Predefined V/f Patterns for Models D211 and B156 to B414

The values in settings 0 to E in the following graphs are specific to 200 V motors; double the values for 400 V motors. Setting

F is for 230 V motors; double the values for 460 V motors.

Table 5.17 Rated Torque Characteristics, Settings 0 to 3

Setting = 0

50 Hz

Setting = 1

60 Hz

Setting = 2

60 Hz

Setting = 3

72 Hz

0

6

200

1.3 2.5

50

12

V

oltage (V)

Frequency (Hz)

0

6

200

1.5 3

60

12

V

oltage (V)

Frequency (Hz)

0

6

12

200

1.5 3

60

50

V

oltage (V)

Frequency (Hz)

0

6

12

200

1.5 3

72

60

V

oltage (V)

Frequency (Hz)

Table 5.18 Derated Torque Characteristics, Settings 4 to 7

Setting = 4

50 Hz

Setting = 5

50 Hz

Setting = 6

60 Hz

Setting = 7

60 Hz

0

5

200

1.3

25

50

35

V

oltage (V)

Frequency (Hz)

0

6

200

1.3

25

50

50

V

oltage (V)

Frequency (Hz)

0

5

200

1.5

30

60

35

V

oltage (V)

Frequency (Hz)

0

6

200

1.5

30

60

50

V

oltage (V)

Frequency (Hz)

Table 5.19 High Starting Torque, Settings 8 to B

Setting = 8

50 Hz

Setting = 9

50 Hz

Setting = A

60 Hz

Setting = B

60 Hz

0

7

200

1.3 2.5

50

15

V

oltage (V)

Frequency (Hz)

0

9

200

1.3 2.5

50

20

V

oltage (V)

Frequency (Hz)

0

7

200

1.5 3

60

15

V

oltage (V)

Frequency (Hz)

0

11

200

1.5 3

60

20

V

oltage (V)

Frequency (Hz)

Table 5.20 Constant Output, Settings C to F

Setting = C

90 Hz

Setting = D

120 Hz

Setting = E

180 Hz

Setting = F

60 Hz

0

6

12

200

1.5 3

90

60

V

oltage (V)

Frequency (Hz)

0

6

12

200

1.5 3

120

60

V

oltage (V)

Frequency (Hz)

0

6

12

200

1.5 3

180

60

V

oltage (V)

Frequency (Hz)

0

6.9

230

1.5 3

60

13.8

V

oltage (V)

Frequency (Hz)

Setting a Custom V/f Pattern (Setting F: Default)

Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameter E1-05.

n

V/f Pattern Settings E1-05

If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the maximum voltage in parameters

E1-05. To create a new V/f pattern, set E1-03 to F.

No.

Parameter Name

Setting Range

Default

E1-05

Maximum Voltage

0.0 to 255.0 V

<1>

230 or 460

Depending on parameter

o2-04, Drive Model

Selection setting.

<1> Values shown are specific to 200 V Class; double the vlue for 400 V class.

5.5 E: Motor Parameters