Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 396

Advertising
background image

Register No.

Contents

0021H

Fault Contents 1
bit 0

Overcurrent (oC), Ground fault (GF)

bit 1

Control Circuit Overvoltage (ov)

bit 2

Overload (oL2)

bit 3

Overheat 1 (oH1), Heatsink Overheat Warning (oH2)

bit 4, 5

Reserved

bit 6

PID Feedback Loss/Excessive PID Feedback (FbL / FbH)

bit 7

EF to EF8: External Fault

bit 8

CPFoo: Hardware Fault (includes oFx)

bit 9

Motor Overload (oL1), Overtorque Detection 1/2 (oL3/oL4), Undertorque Detection 1/2 (UL3/

UL4)

bit A

PG Disconnect (PGo), PG Hardware Fault (PGoH), Overspeed (oS), Speed Deviation (dEv)

bit B

Control Circuit Undervoltage (Uv), Power Supply Undervoltage (AUv), Power Supply Frequency

Fault (Fdv)

bit C

Control Circuit Undervoltage Fault (Uv1), Control Power Supply Voltage Fault (Uv2),

Undervoltage 3 (Uv3), Power Supply Frequency Fault (Fdv), Power Supply Undervoltage (AUv),

Phase Order Detection Fault (SrC)

bit D

Output Phase Loss (LF)

bit E

MEMOBUS/Modbus Communication Error (CE), Option Communication Error (bUS)

bit F

External Digital Operator Connection Fault (oPr)

0022H

Data Link Status
bit 0

Writing data or switching motors

bit 1, 2

Reserved

bit 3

Upper or lower limit error

bit 4

Data conformity error

bit 5

Writing to EEPROM

bit 6

0: Write into EEPROM.

1: Write in RAM only.

Note: Enabled only when H5-17 = 1.

bit 7 to bit F

Reserved

0023H

Frequency Reference

<1>

0024H

Output Frequency

<1>

0025H

Output Voltage Reference, 0.1 V units (units are determined by parameter H5-10)

0026H

Output Current, 0.1 A units

<2>

0027H

Output Power

0028H

Torque Reference

0029H

Fault Contents 2
bit 0

Reserved

bit 1

Ground Fault (GF)

bit 2

Reserved

bit 3

Output Phase Loss (LF)

bit 4, 5

Reserved

bit 6

Motor Overheat 2 (PTC input) (oH4)

bit 7 to bit F

Reserved

D.9 MEMOBUS/Modbus Data Table

396

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual