Table 5.1 Speed Search Activation by Digital Inputs

Setting

Description

b3-24 = 0

b3-24 = 1

61

External Search

Command 1

Closed: Activate Current Detection Speed Search from the

maximum output frequency.

Activate Speed Estimation

Speed Search

62

External Search

Command 2

Closed: Activate Current Detection Speed Search from the

frequency reference.

To activate Speed Search by a digital input, the input must be set together with the Run command or the Run command must

be entered after giving the Speed Search command.
Method 3. After automatic fault restart.
When the number of maximum fault restarts in parameter L5-01 is set higher than 0, the drive will automatically perform

Speed Search as specified by b3-24 following a fault.
Method 4. After momentary power loss.
This mode requires that the Power Loss Ride-Thru function is enabled during CPU operation (L2-01 = 1 or 2).

Refer to L2-01:

Momentary Power Loss Operation Selection on page 183

.

Method 5. After external baseblock is released.
The drive will resume the operation starting with Speed Search if the Run command is present and the output frequency is

above the minimum frequency when the Baseblock command (H1-oo = 8 or 9) is released.

n

b3-01: Speed Search Selection at Start

Determines if Speed Search is automatically performed when a Run command is issued.

No.

Parameter Name

Setting Range

Default

b3-01

Speed Search Selection at Start

0, 1

0

Setting 0: Disabled

This setting starts operating the drive at the minimum output frequency when the Run command is entered. If external Speed

Search 1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.

Setting 1: Enabled

This setting performs Speed Search when the Run command is entered. The drive begins running the motor once Speed Search

is complete.

n

b3-03: Speed Search Deceleration Time

Sets the output frequency reduction ramp used by Current Detection Speed Search (b3-24 = 0) and by the Current Injection

Method of Speed Estimation (b3-24 = 1). The time entered into b3-03 will be the time to decelerate from maximum frequency

(E1-04) to minimum frequency (E1-09).

No.

Name

Setting Range

Default

b3-03

Speed Search Deceleration Time

0.1 to 10.0 s

2.0 s

n

b3-04: V/f Gain during Speed Search

During Speed Search, the output voltage calculated from the V/f pattern is multiplied with this value. Changing this value can

help reduce the output current during Speed Search.

No.

Name

Setting Range

Default

b3-04

V/f Gain during Speed Search

10 to 100%

Determined by

o2-04

n

b3-05: Speed Search Delay Time

In cases where an output contactor is used between the drive and the motor, the contactor must be closed before Speed Search

can be performed. This parameter can be used to delay the Speed Search operation, giving the contactor enough time to close

completely.

No.

Name

Setting Range

Default

b3-05

Speed Search Delay Time

0.0 to 100.0 s

0.2 s

5.2 b: Application

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

137