D: reference settings, D1: frequency reference, 4 d: reference settings – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 156

Advertising
background image

5.4 d: Reference Settings

The figure below gives an overview of the reference input, selections, and priorities.

u

d1: Frequency Reference

n

d1-01 to d1-04: Frequency References 1 to 4

The drive lets the user switch between up to 5 preset frequency references during run (including the Jog reference) through

the digital input terminals. The drive uses the acceleration and deceleration times that have been selected when switching

between each frequency reference.
The Jog frequency overrides all other frequency references and must be selected by a separate digital input.
The multi-speed references 1 and 2 can be provided by analog inputs.

No.

Parameter Name

Setting Range

Default

d1-01 to d1-04

Frequency Reference 1 to 4

0.00 to 400.00 Hz

<1>

<2>

0.00 Hz

<2>

<1> The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01). Parameter d2-01 is

not accessible.

<2> Setting units are determined by parameter o1-03. The default is “Hz” (o1-03 = 0).

Multi-Step Speed Selection

To use several speed references for a multi-step speed sequence, set the Z2-oo (DI-oo Select) parameters to 5 (S5) and 6

(S6). To assign the Jog reference to a digital input, set Z2-oo (DI-oo Select) to 7 (S7) .
Notes on using analog inputs as Multi-Speed 1 and 2:
• The first frequency reference (Multi-Speed 1) comes from the source specified in Z1-07. When using an analog input terminal

to supply the frequency reference, assign the frequency reference source to the control terminals (Z1-07 = 1).

• When an analog input is set to “Auxiliary frequency 1” (H3-02 or H3-10 = 2), the value set to this input will be used as the

Multi-Step Speed 2 instead of the value set to parameter d1-02. If no analog inputs are set for “Auxiliary frequency 1”, then

d1-02 becomes the reference for Multi-Step Speed 2.

Select the different speed references as shown in

Table 5.7

.

Figure 5.15

illustrates the multi-step speed selection.

Table 5.7 Multi-Step Speed Reference and Terminal Switch Combinations

Reference

Multi-Step Speed

Z2-oo = 5

Multi-Step Speed 2

Z2-oo = 6

Jog Reference

Z2-oo = 7

Frequency Reference 1 (set in b1-01)

OFF

OFF

OFF

Frequency Reference 2

(d1-02 or input terminal A1, A2)

ON

OFF

OFF

Frequency Reference 3

(d1-03 or input terminal A1, A2)

OFF

ON

OFF

Frequency Reference 4 (d1-04)

ON

ON

OFF

<1> The Jog frequency overrides all other frequency references.

d1-04

d1-17

ON

ON

ON

ON

ON

Multi-step Speed Ref. 2

Jog Reference

Time

Multi-step Speed Ref. 1

Frequency

reference

d1-01

(A1)

d1-02

(A2)

d1-03

FWD (REV) Run/Stop

Figure 5.15 Preset Reference Timing Diagram

5.4 d: Reference Settings

156

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

Advertising