HOA Keypad Display

Fault Name

FB10

No Drive Comms

Note:

A fault reset is required. An EF0 is not sent to the drive and bypass contactor K3 is not

affected.

An unexpected loss of communication to the drive lasting longer than 15 seconds has been detected.

Cause

Possible Solution

The cable between the bypass controller and the

drive is disconnected or has been damaged.

Verify the cable between the bypass controller board (A2) connector CN6 to drive terminal TB4 is

connected at both ends and is not damaged.

The bypass controller circuit has become

defective.

Replace the bypass control board.

The drive circuitry has become defective.

Replace the drive.

HOA Keypad Display

Fault Name

FB11

Bypass Board Hardware Error

Note:

A fault reset is not required. An EF0 is not sent to the drive. The drive output contactor

K2 and bypass contactor K3 are opened.

The bypass control board failed.

Cause

Possible Solution

An unexpected event occurred with the bypass

controller circuitry.

Replace the bypass controller board.

HOA Keypad Display

Fault Name

FB12

Option Board Comms

Note:

Fault reset will not remove the fault.

Loss of communication to the communication option board. This fault can only occur if the bypass

is programmed to be controlled by the option card (one or more of the following): Z1-07 = 3, Z1-08

= 2, Z1-38 = 2, or Z1-39 = 2.

Cause

Possible Solution

Communication between the option card and

bypass board have timed out and communication

has stopped

Ensure the option card is mounted properly. Replace the option card and cycle power to the bypass

board.

HOA Keypad Display

Fault Name

FB13

Loss of Load

Note:

A fault reset is required. An EF0 fault is sent to the drive and drive output contactor

K2 and bypass contactor K3 are opened.

The conditions were such that it appears the motor has become disconnected from the load.

Cause

Possible Solution

The motor is disconnect from the drive

Check the continuity between the drive/bypass and the motor.

The load has been disconnected from the motor

Check the belt/coupling between the motor and the load

The Loss of Load settings are not proper.

Review and adjust the Loss of Load parameters Z1-31 to Z1-36.

HOA Keypad Display

Fault Name

FB14

Serial Communications Fault

Note:

A fault reset is required. Behavior of the drive and the contactors during an FB14 fault

is determined by parameter Z3-05.

Serial communications timeout

Cause

Possible Solution

Faulty communication wiring or an existing short

circuit.

• Check for faulty serial communication wiring
• Correct the wiring
• Check for disconnected cables and short circuits and repair as needed.

Communication data error occurred due to noise.

• Check the various options available to minimize the effects of noise
• Counteract noise in the control circuit, main circuit, and ground wiring
• Use only recommended cables or other shielded line. Ground the shield on the controller side
• Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors

if required

• Separate all communication wiring from power lines. When the lines must cross, make the lines

cross at a right angle to minimize noise coupling.