L2: momentary power loss ride-thru, Refer to l2-01 – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 183

Advertising
background image

n

L1-02: Motor Overload Protection Time

Sets the detection time of motor overheat due to overload. This setting rarely requires adjustment, but should correlate with

the motor overload tolerance protection time for performing a hot start.

No.

Name

Setting Range

Default

L1-02

Motor Overload Protection Time

0.1 to 50.0 minutes

1.0 minute

Defaulted to operate with an allowance of 150% overload operation for one minute in a hot start.

Figure 5.40

illustrates an example of the electrothermal protection operation time using a general-purpose motor operating at

the value of E1-06, Motor Base Speed, with L1-02 set to one minute.
During normal operation, motor overload protection operates in the area between a cold start and a hot start.
• Cold start: Motor protection operation time in response to an overload situation that was suddenly reached when starting a

stationary motor.

• Hot start: Motor protection operation time in response to an overload situation that occurred during sustained operation at

rated current.

Operation time (minutes)

Cold start

Hot start

Motor current (%)

E2-01 = 100% motor current

10

7

3

1

0.4

0.1

0

100

150

200

Figure 5.40 Motor Protection Operation Time

u

L2: Momentary Power Loss Ride-Thru

n

L2-01: Momentary Power Loss Operation Selection

When a momentary power loss occurs (DC bus voltage falls below the level set in L2-05), the drive can automatically return

to the operation it was performing prior to the power loss based on certain conditions.

No.

Name

Setting Range

Default

L2-01

Momentary Power Loss Operation Selection

0 to 2

2

Setting 0: Disabled

If power is not restored within 15 ms, a Uv1 fault will result and the motor coasts to stop.

Setting 1: Recover within L2-02

When a momentary power loss occurs, the drive output will be shut off. If the power returns within the time set to parameter

L2-02, the drive will perform Speed Search and attempt to resume operation. If the power does not return within this time, it

will trigger a Uv1 fault.

Note:

L2-02 value is dependent on drive model selection and is not accessible.

Setting 2: Recover as long as CPU Has Power

When a momentary power loss occurs, the drive output will be shut off. If the power returns and the drive control circuit has

power, the drive will attempt to perform Speed Search and resume the operation. This will not trigger a Uv1 fault.

Notes on Settings 1 and 2

“Uv” will flash on the operator while the drive is attempting to recover from a momentary power loss. A fault signal is not

output at this time.

5.8 L: Protection Functions

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

183