The PID acceleration/deceleration time can be canceled using a digital input programmed for “PID SFS cancel” (H1-oo =

34).

No.

Name

Setting Range

Default

b5-17

PID Accel/Decel Time

0.0 to 6000.0 s

0.0 s

n

b5-18: PID Setpoint Selection

Enables or disables parameter b5-19 for PID setpoint.

No.

Parameter Name

Setting Range

Default

b5-18

PID Setpoint Selection

0, 1

0

Setting 0: Disabled

Parameter b5-19 is not used as the PID setpoint.

Setting 1: Enabled

Parameter b5-19 is used as PID setpoint.

n

b5-19: PID Setpoint Value

Used as the PID setpoint if parameter b5-18 = 1.

No.

Name

Setting Range

Default

b5-19

PID Setpoint Value

0.00 to 100.00%

0.00%

n

b5-20: PID Setpoint Scaling

Determines the units for the PID Setpoint Value (b5-19) and monitors U5-01 and U5-04. The units for setting and display can

be changed with b5-20.

No.

Parameter Name

Setting Range

Default

b5-20

PID Setpoint Scaling

0 to 3

1

Setting 0: 0.01 Hz

The setpoint and PID monitors are displayed in Hz with a resolution of 0.01 Hz.

Setting 1: 0.01% (100.00%: Maximum Frequency)

The setpoint and PID monitors are displayed as a percentage with a resolution of 0.01%.

Setting 2: r/min (Set the Motor Poles)

The setpoint and PID monitors are displayed in r/min with a resolution of 1 r/min.

Setting 3: User Defined (Determined by b5-38 and b5-39)

Parameters b5-38 and b5-39 determine the units and resolution used to display the values the setpoint in b5-19, and PID

monitors U1-01 and U1-04.

n

b5-34: PID Output Lower Limit

Sets the minimum possible PID controller output as a percentage of the maximum output frequency (E1-04). The lower limit

is disabled when set to 0.00%

No.

Name

Setting Range

Default

b5-34

PID Output Lower Limit

-100.0 to 100.0%

0.00%

n

b5-35: PID Input Limit

Sets the maximum allowed PID input as a percentage of the maximum output frequency (E1-04). Parameter b5-35 acts as a

bipolar limit.

No.

Name

Setting Range

Default

b5-35

PID Input Limit

0.0 to 1000.0%

1000.0%

n

b5-38, b5-39: PID Setpoint User Display, PID Setpoint Display Digits

When parameter b5-20 is set to 3, parameters b5-38 and b5-39 set a user-defined display for the PID setpoint (b5-19) and PID

feedback monitors (U5-01, U5-04).

5.2 b: Application

150

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual