B.2 A: Initialization Parameters

u

A1: Initialization

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

A1-03

(0103)

Initialize Parameters

<1>

Init Parameters

0: No Initialize

1110: User Initialize

2220: 2-Wire Initial

3330: 3-Wire Initial

3410: SELVAL

HVAC Initialize

3420: SELVAL OEM

Bypass Init

0: No initialization

1110: User Initialize (parameter values must be stored using

parameter o2-03)

2220: 2-Wire Initialization

3330: 3-Wire Initialization

3410: HVAC Initialization

3420: OEM Bypass Initialization

Default: 0

Range: 0 to 3420

A1-04

(0104)

Password

Enter Password

When the value set into A1-04 does not match the value set into

A1-05, parameter A1-06 cannot be changed.

Default: 0000

Min.: 0000

Max.: 9999

A1-05

(0105)

Password Setting

Select Password

When the value set into A1-04 does not match the value set into

A1-05, parameter A1-06 cannot be changed.

Default: 0000

Min.: 0000

Max.: 9999

A1-06

(0127)

Application Preset

Application Sel

0: General

1: Fan General

2: Fan PID

3: Fan ReturnAir/PID

4: Cooling Tower

5: CoolingTower/PID

6: Pump Secondary

7: Pump PID

0: Standard

1: Fan

2: Fan with PID Control

3: Return Fan with PID Control

4: Cooling Tower Fan

5: Cooling Tower Fan with PID Control

6: Pump (Secondary)

7: Pump with PID Control

Default: 0

Range: 0 to 7

132

<1> Parameter Z1-01, Initialize, will also initialize all drive parameters.

B.2 A: Initialization Parameters

310

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual