A.3 Drive Derating Data

The drive can be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.

u

Carrier Frequency Derating

Derate the drive according to

Figure A.1

as the carrier frequency increases above the factory default setting.

100

%

90

%

80

%

70

%

4 kHz 6 kHz 8 kHz 10 kHz

0

Figure A.1 Carrier Frequency Derating

A.3 Drive Derating Data

304

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual