B.13 T: Motor Tuning

Enter data into the following parameters to tune the motor and drive for optimal performance. When the drive is not accessible,

the current values of these parameters are not accessible. The default values are set by the Bypass Controller when a Bypass

Control Parameter Initialize (Z1-01 = 1, 2, or 3) command is given.

u

T1: Induction Motor Auto-Tuning

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

T1-01

(0701)

Auto-Tuning Mode

Selection

Tuning Mode Sel

2: Term Resistance

3: On-

DelayCompTune

2: Stationary Auto-Tuning for Line-to-Line Resistance

3: Rotational Auto-Tuning for V/f Control Energy Saving

Default: 2

Range: 2, 3

129

T1-02

(0702)

Motor Rated Power

Mtr Rated Power

Sets the motor rated power as specified on the motor nameplate.

Note:

Use the following formula to convert horsepower

into kilowatts: 1HP = 0.746 kW.

Default:

<1>

Min.: 0.00 kW

Max.: 650.00

kW

129

T1-03

(0703)

Motor Rated Voltage

Rated Voltage

Sets the motor rated voltage as specified on the motor nameplate. Default: 200.0

V

<2>

Min: 0.0
Max: 255.0

<2>

129

T1-04

(0704)

Motor Rated Current

Rated Current

Sets the motor rated current as specified on the motor nameplate. Default:

<1>

Min.: 10% of

drive rated

current

Max.: 150% of

drive rated

current

130

T1-05

(0705)

Motor Base Frequency Rated Frequency

Sets the rated frequency of the motor as specified on the motor

nameplate.

Default: 60.0

Hz

Min.: 0.0

Max.: 400.0

130

T1-06

(0706)

Number of Motor Poles Number of Poles

Sets the number of motor poles as specified on the motor

nameplate.

Default: 4

Min.: 2

Max.: 48

130

T1-07

(0707)

Motor Base Speed

Rated Speed

Sets the rated speed of the motor as specified on the motor

nameplate.

Default: 1750 r/

min

Min.: 0

Max.: 14400

130

T1-11

(070B) Motor Iron Loss

Mtr Iron Loss(W)

Sets the iron loss for determining the Energy Saving coefficient. Default: 14 W

Min.: 0

Max.: 65535

130

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Values shown are specific to 208 Vac. Double the value for 480 Vac.

B.13 T: Motor Tuning

340

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual