B.16 defaults by drive model – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 359

Advertising
background image

Table B.6 400 V Class Drives Default Settings by Drive Model Selection

No.

Name

Unit

Default Settings

Drive Model

4o0034

4o0040

4o0052

4o0065

o2-04

Drive Model Selection

Hex.

9C

9D

9E

9F

b3-04

V/f Gain during Speed Search

%

100

100

100

100

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

0.5

b3-08

Current Control Gain during Speed Search

(Speed Estimation Type)

0.5

0.5

0.5

0.5

C6-02

Carrier Frequency Selection

1

1

1

1

E2-01

Motor Rated Current

A

26.5

32.9

38.6

52.3

E2-03

Motor No-Load Current

A

7.6

7.8

9.2

10.9

L2-02

Momentary Power Loss Ride-Thru Time

s

1

1

1

1.1

L2-03

Momentary Power Loss Minimum Baseblock

Time

s

0.6

0.6

0.6

0.6

L8-02

Overheat Alarm Level

°C

130

130

130

130

L8-38

Carrier Frequency Reduction Selection

1

1

1

1

Table B.7 400 V Class Drives Default Settings by Drive Model Selection

No.

Name

Unit

Default Settings

Drive Model

4o0077

4o0096

4o0124

4o0156

o2-04

Drive Model Selection

Hex.

A1

A2

A3

A4

b3-04

V/f Gain during Speed Search

%

100

100

80

60

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

0.7

b3-08

Current Control Gain during Speed Search

(Speed Estimation Type)

0.5

0.5

0.5

0.8

C6-02

Carrier Frequency Selection

1

1

1

1

E2-01

Motor Rated Current

A

65.6

79.7

95

130

E2-03

Motor No-Load Current

A

19.1

22

24

36

L2-02

Momentary Power Loss Ride-Thru Time

s

1.1

1.2

1.2

1.3

L2-03

Momentary Power Loss Minimum Baseblock

Time

s

0.6

0.6

1

1

L8-02

Overheat Alarm Level

°C

130

130

130

130

L8-38

Carrier Frequency Reduction Selection

1

1

1

1

Table B.8 400 V Class Drives Default Settings by Drive Model Selection

No.

Name

Unit

Default Settings

Drive Model

4o0180

4o0216

4o0240

4o0302

4o0361

4o0414

o2-04

Drive Model Selection

Hex.

A5

A6

A7

A8

A9

AA

b3-04

V/f Gain during Speed Search

%

60

60

60

60

60

60

b3-06

Output Current 1 during Speed Search

0.7

0.7

0.7

0.7

0.7

0.7

b3-08

Current Control Gain during Speed

Search

(Speed Estimation Type)

0.8

0.8

0.8

0.8

0.8

0.8

C6-02

Carrier Frequency Selection

1

1

1

1

1

1

E2-01

Motor Rated Current

A

156

190

223

270

310

370

E2-03

Motor No-Load Current

A

40

49

58

70

81

96

L2-02

Momentary Power Loss Ride-Thru

Time

s

1.5

1.7

1.7

1.8

1.9

2

L2-03

Momentary Power Loss Minimum

Baseblock Time

s

1

1

1

1

1

1

L8-02

Overheat Alarm Level

°C

130

130

130

130

130

130

L8-38

Carrier Frequency Reduction

Selection

1

1

1

1

1

1

B.16 Defaults by Drive Model

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

359

B

Parameter List