Motor is too hot – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 269

Advertising
background image

n

Motor Rotates in the Opposite Direction from the Run Command

Cause

Possible Solutions

Phase wiring between the drive and motor is incorrect.

• Check the motor wiring.
• Switch two motor cables (U, V, and W) to reverse motor direction.
• Connect drive output terminals U/T1, V/T2, and W/T3 in the right order to match motor

terminals U, V, and W.

• Change the setting of parameter b1-14.

The forward direction for the motor is set up incorrectly.

Typically, forward is designated as being counterclockwise when looking from the motor shaft

(see figure below).

1

2

1.

Forward Rotating Motor (looking down the motor shaft)

2.

Motor Shaft

The motor is running at almost 0 Hz and the Speed

Search estimated the speed to be in the opposite

direction.

• Disable bi-directional search (b3-14 = 0) so that Speed Search is performed only in the

specified direction.

Note:

Check the motor specifications for the forward and reverse directions. The motor specifications will vary depending on the manufacturer

of the motor.

n

Motor Rotates in One Direction Only

Cause

Possible Solutions

The drive prohibits reverse rotation.

• Check parameter b1-04.
• Set parameter b1-04 to 0 to allow the motor to rotate in reverse.

A Reverse run signal has not been entered, although

3-Wire sequence is selected.

• Make sure that one of the input terminals S3 to S8 used for the 3-Wire sequence has been set

for reverse.

u

Motor is Too Hot

Cause

Possible Solutions

The load is too heavy.

If the load is too heavy for the motor, the motor will overheat as it exceeds its rated torque value

for an extended period of time.

Keep in mind that the motor also has a short-term overload rating in addition to the possible

solutions provided below:
• Reduce the load.
• Increase the acceleration and deceleration times.
• Check the values set for the motor protection (L1-01, L1-02) as well as the motor rated current

(E2-01).

• Increase motor capacity.

The air around the motor is too hot.

• Check the ambient temperature.
• Cool the area until it is within the specified temperature range.

Insufficient voltage insulation between motor phases.

When the motor cable is long, high voltage surges occur between the motor coils and drive

switching.

Normally, surges can reach up to three times the drive input power supply voltage.
• Use a motor with a voltage tolerance higher than the max voltage surge.
• Use an inverter-duty motor rated for use with AC drives when using the motor on drives rated

higher than 208 V.

• Install an AC reactor on the output side of the drive. The carrier frequency should be set to 2

kHz when installing an AC reactor.

The motor fan has stopped or is clogged.

Check the motor fan.

The carrier frequency is too low.

Increase the carrier frequency to lower the current harmonic distortion and lower the motor

temperature.

6.9 Troubleshooting without Fault Display

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

269

6

Diagnostics & Troubleshooting