D: references, D1: frequency reference, D2: frequency upper/lower limits – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 318: D3: jump frequency, B.5 d: references

Advertising
background image

B.5 d: References

Reference parameters set the various frequency reference values during operation.

u

d1: Frequency Reference

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

d1-01

(0280)

Frequency Reference 1 Reference 1

Sets the frequency reference for the drive. Setting units are

determined by parameter o1-03.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

156

d1-02

(0281)

Frequency Reference 2 Reference 2

Sets the frequency reference for the drive. Setting units are

determined by parameter o1-03.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

156

d1-03

(0282)

Frequency Reference 3 Reference 3

Sets the frequency reference for the drive. Setting units are

determined by parameter o1-03.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

156

d1-04

(0283)

Frequency Reference 4 Reference 4

Sets the frequency reference for the drive. Setting units are

determined by parameter o1-03.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

156

d1-17

(0292)

Jog Frequency

Reference

Jog Reference

Sets the Jog frequency reference. Setting units are determined

by parameter o1-03.

Default: 6.00 Hz

Min.: 0.00
Max.: 400.00

<1>

<1> Range upper limit is determined by parameters d2-01, Frequency Reference Upper Limit.

u

d2: Frequency Upper/Lower Limits

No.

(Addr.

Hex.)

Name

LCD Display

Description

Setting

Page

d2-01

(0289)

Frequency Reference

Upper Limit

Ref Upper Limit

Sets the frequency reference upper limit as a percentage of the

maximum output frequency.

Default: 100.0%

Min.: 0.0

Max.: 110.0

157

d2-02

(028A)

Frequency Reference

Lower Limit

Ref Lower Limit

Sets the frequency reference lower limit as a percentage of the

maximum output frequency.

Default: 0.0%

Min.: 0.0

Max.: 110.0

157

d2-03

(0293)

Master Speed Reference

Lower Limit

Ref1 Lower Limit

Sets the lower limit for frequency references from analog inputs

as a percentage of the maximum output frequency.

Default: 0.0%

Min.: 0.0

Max.: 110.0

157

u

d3: Jump Frequency

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

d3-01

(0294)

Jump Frequency 1

Jump Freq 1

Eliminates problems with resonant vibration of the motor/

machine by avoiding continuous operation in predefined

frequency ranges. The drive accelerates and decelerates the

motor through the prohibited frequency ranges.

Setting 0.0 disables this function.

Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

158

d3-02

(0295)

Jump Frequency 2

Jump Freq 2

Eliminates problems with resonant vibration of the motor/

machine by avoiding continuous operation in predefined

frequency ranges. The drive accelerates and decelerates the

motor through the prohibited frequency ranges.

Setting 0.0 disables this function.

Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

158

B.5 d: References

318

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual