Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 222

Advertising
background image

No.

Name

Setting Range

Default

Z3-07

Serial Communications Receive to Transmit Wait Time

0 to 99 ms

5 ms

n

Z3-08, Z3-09: BACnet Device Object Identifier

These parameters set the Instance Identifier of the BACnet Device Object, where Z3-08 is the least significant word and Z3-09

is the most significant word.

No.

Name

Setting Range

Default

Z3-08

BACnet Device Object Identifier 0

0 to FFFFH

1

Z3-09

BACnet Device Object Identifier 1

0 to 003FH

0

Example 1: Set Device Object Instance Identifier of “1234”.
1234 decimal is equal to 4D2H (hexadecimal).
Set Z3-08 to 4D2H and set Z3-09 to 0.
Example 2: Set Device Object Instance Identifier of “123456”.
123456 decimal is equal to 1E240H.
Set Z3-08 to D687H and set Z3-09 to 12H.

n

Z3-10: Cable Loss Pre-set Speed

Sets the frequency reference when a serial communications fault is detected and Z3-05 is set to 4.

No.

Name

Setting Range

Default

Z3-10

Cable Loss Pre-set Speed

0.0 to 60.0 Hz

0.0 Hz

n

Z3-11: Communication Fault Detection Selection

No.

Name

Setting Range

Default

Z3-11

Communication Fault Detection Selection

0 to 1

1

Setting 0: Disabled

Ignore setting in Z3-05.

Setting 1: Enabled

Behavior defined by Z3-05.

n

Z3-12: Network Digital Input Select

Determines whether the serial communication digital input simulation is active.

No.

Name

Setting Range

Default

Z3-12

Network Digital Input Select

0, 1

0

Setting 0: Disable

Serial communications physical digital inputs are ignored.
For MEMOBUS/Modbus (Z3-01 = 0): Command Register 8402H is disabled.
For Metasys N2 (Z3-01 = 1): Binary Outputs B05, B06, B07, B08, and B09 are disabled.
For P1 Apogee (Z3-01 = 2): Points LDO44, LDO45, LDO46, LDO47, and LDO48 are disabled.
For BACnet (Z3-01 = 3): BV72, BV73, BV74, BV75, BV76, BV77, BV78, and BV79 are disabled.

Setting 1: Enable

Physical digital inputs S1 to S8 are logically OR’d with the serial communications digital inputs.

WARNING! Sudden Movement Hazard. Setting this parameter to 1 may cause the system to run unexpectedly or not stop when required

even if the physical digital input is de-energized, resulting in death or serious injury. Clear all personnel from the drive, motor and machine

area before applying power. Set this parameter to 0 to prevent serial communications from triggering undesired and unexpected system

operation.

5.14 Z: Bypass Parameters

222

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual