Motor Does Not Rotate

Cause

Possible Solutions

The drive is not in the Drive Mode.

• Check if the DRV light on the HOA keypad is lit.
Enter the Drive Mode to begin operating the motor.

Refer to The Drive and Programming Modes on page

118

.

The HAND button was pressed.

Stop the drive and check if the correct frequency reference source is selected. If the operator keypad shall be the

source, the HAND button LED must be on. If the source is REMOTE, it must be off.

Press the HAND button to solve the problem.

Auto-Tuning has just completed.

• When Auto-Tuning completes, the drive is switched back to the Programming Mode. The Run command will

not be accepted unless the drive is in the Drive Mode.

• Use the HOA keypad to enter the Drive Mode.

Refer to The Drive and Programming Modes on page 118

.

A Fast Stop was executed and has

not yet been reset.

Reset the Fast Stop command.

Settings are incorrect for the source

that provides the Run command.

Check parameter b1-02 (Run Command Selection).

Set b1-02 so that it corresponds with the correct Run command source.

0: HOA keypad

1: Control circuit terminal (default setting)

2: MEMOBUS/Modbus communications

3: Option card

There is faulty wiring in the control

circuit terminals.

• Check the wiring for the control terminal.
• Correct wiring mistakes.
• Check the input terminal status monitor (U1-10).

The drive has been set to accept the

frequency reference from the

incorrect source.

Check parameter b1-01 (Frequency Reference Selection 1).

Set b1-01 to the correct source of the frequency reference.

0: HOA keypad

1: Control circuit terminal (default setting)

2: MEMOBUS/Modbus communications

3: Option card

The terminal set to accept the main

speed reference is set to the incorrect

voltage and/or current.

If the frequency reference is set at terminal A1, check parameter H3-01 for the correct signal level selection. If

terminal A2 is used, check parameter H3-09. If terminal A3 is used, check parameter H3-06.

Refer to Terminals

A1, A2, and A3 Input Signal Selection on page 105

.

Selection for the sink/source mode

and the internal/external power

supply is incorrect.

Check wire jumper connection between terminals SC and SP.

Frequency reference is too low.

• Check the frequency reference monitor (U1-01).
• Increase the frequency by changing the maximum output frequency (E1-09).

Multi-function analog input is set up

to accept gain for the frequency

reference, but no voltage (current)

has been provided.

• Check the multi-function analog input settings.
• Check if analog input A1, A2, or A3 is set for frequency reference gain (H3-02, H3-10, H3-06 = 1). If so, check

if the correct signal is applied to the terminal. The gain and the frequency reference will be 0 if no signal is

applied to the gain input.

• Check if H3-02, H3-10, and H3-06 have been set to the proper values.
• Check if the analog input value has been set properly. (U1-13 to U1-15)

The OFF button was pressed when

the drive was started from a

REMOTE source.

• Pressing the OFF button will decelerate the drive to stop.
• Switch off the Run command and then re-enter a new Run command.
• Set o2-02 to 0 to disable the OFF button.

Motor starting torque is too low.

Refer to Motor Performance Fine-Tuning on page 230

.

Frequency reference value is too low

or the drive does not accept the value

entered.

Enter a value that is above the minimum output frequency determined by E1-09.

The sequence Start/Stop sequence is

set up incorrectly.

• If the drive is supposed to be set up for a 2-wire sequence, then ensure parameters H1-03 through H1-08 are not

set to 0.

• If the drive is supposed to be set up for a 3-wire sequence, then one of the parameters H1-03 through H1-08 must

be set to 0. Terminal S1 will become the Start, terminal S2 will become the Stop input.

6.9 Troubleshooting without Fault Display

268