HOA Keypad Display

Minor Fault Name

EF

Forward/Reverse Run Command Input Error
Both forward run and reverse run closed simultaneously for longer than 0.5 s.

Cause

Possible Solutions

Sequence error

Check the forward and reverse command sequence and correct the problem.

Note:

When minor fault EF detected, motor ramps to stop.

HOA Keypad Display

Minor Fault Name

EF0

Option Card External Fault
An external fault condition is present.

Cause

Possible Solutions

An external fault was received from the PLC with

F6-03 set to 3, which allows the drive to continue

running after an external fault occurs

• Remove the cause of the external fault.
• Remove the external fault input from the PLC.

There is a problem with the PLC program

Check the PLC program and correct problems.

HOA Keypad Display

Minor Fault Name

EF1

External Fault (Input Terminal S1)
External fault at multi-function input terminal S1.

EF2

External fault (input terminal S2)
External fault at multi-function input terminal S2.

EF3

External fault (input terminal S3)
External fault at multi-function input terminal S3.

EF4

External fault (input terminal S4)
External fault at multi-function input terminal S4.

EF5

External fault (input terminal S5)
External fault at multi-function input terminal S5.

EF6

External fault (input terminal S6)
External fault at multi-function input terminal S6.

EF7

External fault (input terminal S7)
External fault at multi-function input terminal S7.

EF8

External fault (input terminal S8)
External fault at multi-function input terminal S8.

Cause

Possible Solutions

An external device has tripped an alarm function Remove the cause of the external fault and reset the multi-function input value.

Wiring is incorrect

• Ensure the signal lines have been connected properly to the terminals assigned for external fault

detection (H1-oo = 24).

• Reconnect the signal line.

Multi-function contact inputs are set incorrectly

• Check if the unused terminals have been set for H1-oo = 24 (External Fault).
• Change the terminal settings.

HOA Keypad Display

Minor Fault Name

FbH

Excessive PID Feedback
The PID feedback input is higher than the level set to b5-36 for longer than the time set to b5-37, and

b5-12 is set to 1 or 4.

Cause

Possible Solutions

Parameter settings for b5-36 and b5-37 are

incorrect

Check parameters b5-36 and b5-37.

PID feedback wiring is faulty

Correct the wiring.

Feedback sensor has malfunctioned

Check the sensor and replace it if damaged.

Feedback input circuit is damaged

Replace either the control board or the entire drive. For instructions on replacing the control board,

contact Yaskawa or your nearest sales representative.