7 h: terminal functions – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 168

Advertising
background image

Setting

Function

Page

16

Frequency Detection 4

172

17

Torque Detection 1 (N.C.)

171

1A

During Reverse

173

1B

During Baseblock 2 (N.C.)

173

1E

Restart Enabled

173

20

Drive Overheat Pre-Alarm (oH)

173

2F

Maintenance Period

173

37

During Run 2

173

38

Drive Enable

174

Setting

Function

Page

39

Energy Pulse Output

174

3A

Regenerated Power Pulse Output

174

3D

During Speed Search

174

4C

During Fast Stop

174

4D

oH Pre-Alarm Time Limit

174

60

Internal Cooling Fan Alarm

174

64

During Commercial Power Operation

174

100 to 164 Functions 0 to 64 with Inverse Output

174

Setting 0: During Run

The output closes when the drive is outputting a voltage.

Status

Description

Open

Drive is stopped.

Closed

A Run command is input or the drive is in deceleration or DC injection.

ON

ON

OFF

OFF

ON

OFF

Run command

Baseblock

command

Output

frequency

During Run

Figure 5.20 During Run Time Chart

Setting 1: Zero Speed

The output closes when the output frequency or motor speed falls below the minimum output frequency set to E1-09 or b2-01.

Status

Description

Open

Output frequency is above the minimum output frequency set to E1-09 or b2-01

Closed

Output frequency is less than the minimum output frequency set to E1-09 or b2-01

OFF

Output frequency

or

motor speed

Zero Speed

ON

E1-09 (Max. Output Frequency) or
b2-01 (Zero Speed Level)

Figure 5.21 Zero-Speed Time Chart

Setting 2: Speed Agree 1 (f

ref

/f

out

Agree 1)

The output closes when the actual output frequency or motor speed is within the Speed Agree Width (L4-02) of the current

frequency reference regardless of the direction.

Status

Description

Open

Output frequency or motor speed does not match the frequency reference while the drive is running.

Closed

Output frequency or motor speed is within the range of frequency reference ±L4-02.

Note:

Detection works in forward and reverse.

5.7 H: Terminal Functions

168

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual