7 h: terminal functions – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 169

Advertising
background image

L4-02

L4-02

Frequency
reference

Speed agree 1

ON

OFF

Output Frequency

or Motor Speed

Figure 5.22 Speed Agree 1 Time Chart

Setting 3: User-Set Speed Agree 1 (f

ref

/f

set

Agree 1)

The output closes when the actual output frequency or motor speed and the frequency reference are within the speed agree

width (L4-02) of the programmed speed agree level (L4-01).

Status

Description

Open

Output frequency or motor speed and frequency reference are not both within the range of L4-01 ±L4-02.

Closed

Output frequency or motor speed and the frequency reference are both within the range of L4-01 ±L4-02.

Note:

Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.

Frequency reference

Frequency reference

+

L4-02

Frequency reference – L4-02

L4-01

L4-01

+

L4-02

L4-01 – L4-02

Frequency reference

Frequency reference

+

L4-02

Frequency reference – L4-02

–L4-01

–L4-01

+

L4-02

–L4-01 – L4-02

During

Forward

During Reverse

Output frequency

0 Hz

OFF

OFF

OFF

ON

ON

ON

ON

Output frequency

User Set
Speed Agree 1

Figure 5.23 User Set Speed Agree 1 Time Chart

Setting 4: Frequency Detection 1

The output opens when the output frequency or motor speed rises above the detection level set in L4-01 plus the detection

width set in L4-02. The terminal remains open until the output frequency or motor speed fall below the level set in L4-01.

Status

Description

Open

Output frequency or motor speed exceeded L4-01 + L4-02.

Closed

Output frequency or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.

Note:

Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.

5.7 H: Terminal Functions

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

169

5

Programming