Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 398

Advertising
background image

Register No.

Contents

002EH

Reserved

002FH

Frequency Reference Bias (from Up/Down 2 Function), 0.1% units

0030H

Reserved

0031H

Control Circuit Voltage, 1 Vdc units

0032H

Torque Reference (U1-09), 0.1% units

0033H

Reserved

0034H

Product Code 1 [ASCII], Product Type (U0 for U1000)

0035H

Product Code 2 [ASCII], Region Code

0036H, 0037H

Reserved

0038H

PID Feedback, 0.1% units, unsigned, 100% / max. output frequency

0039H

PID Input, 0.1% units, signed, 100% / max. output frequency

003AH

PID Output, 0.1% units, signed, 100% / max. output frequency

003BH, 003CH

Reserved

003DH

Communications Error Contents

<3>

bit 0

CRC Error

bit 1

Data Length Error

bit 2

Reserved

bit 3

Parity Error

bit 4

Overrun Error

bit 5

Framing Error

bit 6

Timeout

bit 7 to bit F

Reserved

003EH

Output Frequency

r/min

<4>

003FH

0.01% units

0040H to 004AH

Used for various monitors U1-oo.

Refer to U: Monitors on page 341

for parameter details.

004BH

Drive status (U1-12)
bit 0

During Run

bit 1

During Zero Speed

bit 2

During Reverse Run

bit 3

During Fault Reset Signal Input

bit 4

During Speed Agree

bit 5

Drive Ready

bit 6

Alarm

bit 7

Fault

bit 8

During Operation Error (oPEoo)

bit 9

During Momentary Power Loss

bit A

Motor 2 selected

bit B

Reserved

bit E

ComRef status, NetRef status

bit F

ComCtrl status, NetCtrl status

004CH to 007EH

Used for monitors U1-oo, U4-oo, U5-oo and U6-oo.

Refer to U2: Fault Trace on page 344

and

Refer to U3: Fault

History on page 345

for parameter details.

007FH

Minor Fault Code,

Refer to Alarm Register Contents on page 410

for Minor Fault codes.

0080H to 0097H

Used for monitors U2-oo, U3-oo.

Refer to U: Monitors on page 341

for parameter details and

Refer to Fault Trace

Contents on page 408

for register value descriptions.

0098H, 0099H

U4-01 (Cumulative Operation Time)

Example: When U4-01 (Cumulative Operation Time) is 12345 hours, then 0098H = 1234 and 0099H = 5.

009AH, 009BH

U4-03 (Cooling Fan Operation Time)

Example: When U4-03 (Cooling Fan Operation Time) is 12345 hours, then 009AH = 1234 and 009BH = 5.

009CH to 00AAH

Reserved

00ABH

Drive Rated Current

<2>

D.9 MEMOBUS/Modbus Data Table

398

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual