u

Sound from Motor

Cause

Possible Solutions

Exceeded 110% of the rated output current of the drive

while operating at low speeds.

• If the output current rises too high at low speeds, the carrier frequency is automatically reduced

and causes a whining or buzzing sound.

• If the sound is coming from the motor, disable carrier frequency derating (L8-38 = 0).
• Disabling the automatic carrier frequency derating increases the chances of an overload fault

(oL2). Switch to a larger capacity motor if oL2 faults occur too frequently.

u

Motor Does Not Restart after Power Loss

Cause

Possible Solutions

The Run command was not issued again when power

was restored.

• Check the sequence and wiring that has been set up to enter the Run command.
• A relay should be set up to make sure the Run command remains enabled throughout any power

loss.

The relay that is supposed to maintain the Run

command has been switched off.

Check wiring and circuitry for the relay intended to keep the Run command enabled.

u

The Safety Controller Does Not Recognize Safe Disable Monitor Output Signals
(Terminals DM+ and DM-)

Cause

Possible Solutions

There is faulty wiring in the Safe Disable monitor

output terminals.

• Check the Safe Disable monitor output terminal wiring.
• Correct any wiring mistakes.

6.9 Troubleshooting without Fault Display

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

273

6

Diagnostics & Troubleshooting