No.

Name

Setting Range

Default

H4-05

Multi-Function Analog Output Terminal AM Gain

-999.9 to 999.9%

50.0%

H4-06

Multi-Function Analog Output Terminal AM Bias

-999.9 to 999.9%

0.0%

Using Gain and Bias to Adjust Output Signal Level

When viewing a gain setting parameter (H4-02 or H4-05) on the HOA keypad, the analog output will supply a voltage signal

equal to 100% of the monitor value (including changes made from bias and gain settings). When viewing a bias setting

parameter (H4-03 or H4-06), the analog output voltage will supply a signal equal to 0% monitor value.
Example 1: Set H4-02 to 50% for an output signal of 5 V at terminal FM when the monitored value is at 100%.
Example 2: Set H4-02 to 150% for an output signal of 10 V at terminal FM when the monitored value is at 76.7%.

Output Voltage

Output Voltage

0 V

5 V

10 V

Gain 150%
Bias 0%

Gain = 150%
Bias = 0%

Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%

Gain 100%
Bias 0%

Gain 50%
Bias 0%

100%

Monitor Value

Monitor Value

0%

H4-07, 08 = 0

H4-07, 08 = 1

10 V

-10 V

100%

5 V

15 V

-5 V

-15 V

-100%

Figure 5.37 Analog Output Gain and Bias Setting Example 1 and 2

Example 3: Set H4-03 to 30% for an output signal of 3 V at terminal FM when the monitored value is at 0%.

Gain = 100%
Bias = 30%

Gain = 100%
Bias = 0%

Gain 100%

Bias 30%

Gain 100%

Bias 0%

Monitor Value

Monitor Value

0 V

3 V

10 V

100%

0%

Output Voltage

Output Voltage

H4-07, 08 = 0

H4-07, 08 = 1

10V

-10 V

100%

3 V

-4 V

-100%

Figure 5.38 Analog Output Gain and Bias Setting Example 3

n

H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection

Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters

H4-07 and H4-08.
Set jumper S5 on the terminal board accordingly when changing these parameters.

No.

Name

Setting Range

Default

H4-07

Multi-Function Analog Output Terminal FM

Signal Level Selection

0 to 2

0

H4-08

Multi-Function Analog Output Terminal AM

Signal Level Selection

0 to 2

0

Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Setting 2: 4 to 20 mA

5.7 H: Terminal Functions