Z4: bypass control option boards – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 355

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

Z3-05

(8504) Serial Communications

Fault Select

Fault Sel

0: Ignore

1: Alarm only

2: Fault Send EF0

3: Flt EF0 Open K3

4: Alarm(Z3-10)

Selects the action to take when a serial communications fault is

detected.

0: Ignore. A serial communications loss will result in no action

being taken.

1: Alarm only.

2: Fault with EF0. An EF0 will be sent to the drive. If running in

Bypass mode, the bypass contactor will NOT open and the motor

will keep running.

3: Fault with EF0 and Open Contactors. An EF0 fault will be sent

to the drive and the bypass contactor (K3) will be opened.

4: Alarm and run at preset speed set in Z3-10. Display AL14

alarm on Operator.

Default: 1

Range: 0 to 4

221

Z3-06

(8505) Serial Communications

Fault Time Select

Fault Time

Sets the time allowed to elapse since receiving serial

communications before triggering a communications fault.

A setting of 0.0 will never time out.

Default: 2.0 s

Min.: 0.0

Max.: 99.9

221

Z3-07

(8506)

Serial Communications

Receive to Transmit

Wait Time

Rx to Tx Wait

Sets the time to delay a serial communications response to a serial

communications command.

Default: 5 ms

Min.: 0

Max.: 99

221

Z3-08

(8507) BACnet Device Object

Identifier 0

BAC Dev ID0

BACnet only.

Sets the least significant word of 22-bit virtual address.

Default: 1

Min.: 0

Max.: FFFF

222

Z3-09

(8508) BACnet Device Object

Identifier 1

BAC Dev ID1

BACnet only.

Sets the most significant word of 22-bit virtual address.

Default: 0

Min.: 0

Max.: 003F

222

Z3-10

(8509) Cable Loss Preset

Frequency

Cable Loss Freq

When a serial communications fault is detected and Z3-05=4, the

resulting value will become the frequency reference.

Default: 0.0 Hz

Min.: 0.0

Max.: 60.0

222

Z3-11

(850A) Communication Fault

Detection Selection

Serial Fault Det

0: Disabled

1: Enabled

Communication Fault Detection Selection

0: Disabled. Serial communications fault detection is completely

disabled.

1: Enabled. Behavior defined by Z3-05.

Default: 1

Range: 0, 1

222

Z3-12

(850B)

Network Digital Input

Select

Network Dig Inp

0: Disabled

1: Enabled

Enables and disables control of the digital inputs over a network.

Wiring to the physical digital input is not required.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

222

u

Z4: Bypass Control Option Boards

No.

(Addr.

Hex)

Name

Description

Values

Page

Z4-01

(8700)

IP Address 1

Sets the most significant octet of network static IP address.

Default: 192

Range: 0 to 255

223

Z4-02

(8701)

IP Address 2

Sets the second most significant octet of network static IP address.

Default: 168

Range: 0 to 255

223

Z4-03

(8702)

IP Address 3

Sets the third most significant octet of network static IP address.

Default: 1

Range: 0 to 255

223

Z4-04

(8703)

IP Address 4

Sets the fourth most significant octet of network static IP address.

Default: 20

Range: 0 to 255

223

Z4-05

(8704)

Subnet Mask 1

Sets the most significant octet of network static subnet mask.

Default: 255

Range: 0 to 255

223

B.15 Z: Bypass Parameters

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

355

B

Parameter List