L3: stall prevention, L4: speed detection – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 331

Advertising
background image

u

L3: Stall Prevention

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L3-01

(048F)

Stall Prevention

Selection during

Acceleration

StallP Accel Sel

0: Disabled

1: General purpose

2: Intelligent

3: iLim Mode

0: Disabled.

1: General purpose. Acceleration is paused as long as the

current is above the L3-02 setting.

2: Intelligent. Accelerate in the shortest possible time without

exceeding the L3-02 level.

3: Enabled (Current Limit). The acceleration rate is

automatically adjusted while limiting the output current at the

setting value of the stall prevention level (L3-02).

Default: 1

Range: 0 to 3

L3-02

(0490)

Stall Prevention Level

during Acceleration

StallP Accel Lvl

Used when L3-01 = 1 or 2. 100% is equal to the drive rated

current.

Default:

<1>

Min.: 0%
Max.: 150%

<1>

184

L3-03

(0491)

Stall Prevention Limit

during Acceleration

StallPAccDecLim

Sets Stall Prevention lower limit during acceleration when

operating in the constant power range. Set as a percentage of

drive rated current.

Default: 50%

Min.: 0

Max.: 100

185

L3-04

(0492)

Stall Prevention

Selection during

Deceleration

StallP Decel Sel

0: Disabled

1: General Purpose

4: High Flux Brake

6: ILim Mode

0: Disabled. Deceleration at the active deceleration rate. An ov

fault may occur.

1: General purpose. Deceleration is paused when the DC bus

voltage exceeds the Stall Prevention level.

4: Overexcitation Deceleration. Decelerates while increasing

the motor flux

6: Enable (Current Limit). The deceleration rate is

automatically adjusted while limiting the regeneration current

at the setting value of the stall prevention level (L3-14).

Default: 1

Range: 0, 1, 4, 6

185

L3-05

(0493)

Stall Prevention

Selection during Run

StallP Run Sel

0: Disabled

1: Decel time

2: Decel time 2

0: Disabled. Drive runs at a set frequency. A heavy load may

cause speed loss.

1: Decel time 1. Uses the deceleration time set to C1-02 while

Stall Prevention is performed.

2: Decel time 2. Uses the deceleration time set to C1-04 while

Stall Prevention is performed.

Default: 1

Range: 0 to 2

L3-06

(0494)

Stall Prevention Level

during Run

StallP Run Level

Enabled when L3-05 is set to 1 or 2. 100% is equal to the drive

rated current.

Default:

<1>

Min.: 30%
Max.: 150%

<1>

186

L3-14

(04C7)

Stall Prevention Level

during Deceleration

StallP Decel Lvl

Used when L3-04 = 1. 100% is equal to the drive rated current.

Default: 120%

Min.: 80
Max.: 120

<1>

L3-23

(04FD)

Automatic Reduction

Selection for Stall

Prevention during Run

CHP Stall P Sel

0: Lv1 set in L3-06

1: Autom. Reduction

0: Sets the Stall Prevention level set in L3-04 that is used

throughout the entire frequency range.

1: Automatic Stall Prevention level reduction in the constant

output range. The lower limit value is 40% of L3-06.

Default: 0

Range: 0, 1

<1> Upper limit and default values are dependent on parameter L8-38, Frequency Reduction Selection.

u

L4: Speed Detection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L4-01

(0499)

Speed Agreement

Detection Level

Spd Agree Level

Sets the frequency detection level for digital output functions

H2-oo = 2, 3, 4, 5.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

186

L4-02

(049A)

Speed Agreement

Detection Width

Spd Agree Width

Sets the hysteresis or allowable margin for speed detection.

Default: 2.0 Hz

Min.: 0.0

Max.: 20.0

186

L4-03

(049B)

Speed Agreement

Detection Level (+/-) Spd Agree Lvl+-

Sets the frequency detection level for digital output functions

H2-oo = 13, 14, 15, 16.

Default: 0.0 Hz

Min.: -400.0

Max.: 400.0

186

L4-04

(049C)

Speed Agreement

Detection Width (+/-) Spd Agree Wdth+-

Sets the hysteresis or allowable margin for speed detection.

Default: 2.0 kHz

Min.: 0.0

Max.: 20.0

186

L4-05

(049D)

Frequency Reference

Loss Detection

Selection

Ref Loss Sel

0: Stop

1: Run@L4-06PrevRef

0: Stop. Drive stops when the frequency reference is lost.

1: Run. Drive runs at a reduced speed when the frequency

reference is lost.

Default: 1

Range: 0, 1

186

B.9 L: Protection Function

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

331

B

Parameter List