Figure 5.51, Sequence timer example 3 – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 203

Advertising
background image

Mon

0:00

Sequence Timer 2

1:00

(cont.)

2:00
3:00
4:00
5:00
6:00

Sequence Timer 2

Run at d1-03

7:00
8:00
9:00

10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00

Sequence Timer 1

Run at d1-01

Sun

Sat

Fri

Thur

Wed

Tue

Figure 5.51 Sequence Timer Example 2

n

Sequence Timer Example 3

Set the parameters as shown in

Table 5.26

to accomplish the timer sequencing in

Figure 5.52

.

Table 5.26 Sequence Timer Example 3 Parameter Settings

No.

Name

Setting

Comment

S2-01

Sequence Timer 1 Start Time

05:00

S2-02

Sequence Timer 1 Stop Time

15:00

S2-03

Sequence Timer 1 Day Selection

2

Mon to Fri

S2-04

Sequence Timer 1 Selection

1

Run

S2-05

Sequence Timer 1 Reference Source

0

Operator (d1-01)

S2-06

Sequence Timer 2 Start Time

15:00

S2-07

Sequence Timer 2 Stop Time

22:00

S2-08

Sequence Timer 2 Day Selection

2

Mon to Fri

S2-09

Sequence Timer 2 Selection

2

Run PID Disable

S2-10

Sequence Timer 2 Reference Source

1

Operator (d1-02)

S2-11

Sequence Timer 3 Start Time

09:00

S2-12

Sequence Timer 3 Stop Time

24:00

S2-13

Sequence Timer 3 Day Selection

9

Sat

S2-14

Sequence Timer 3 Selection

1

Run

S2-15

Sequence Timer 3 Reference Source

2

Operator (d1-03)

S2-16

Sequence Timer 4 Start Time

0:00

n/a

S2-17

Sequence Timer 4 Stop Time

0:00

n/a

S2-18

Sequence Timer 4 Day Selection

0

Timer Disabled

S2-19

Sequence Timer 4 Selection

0

n/a

S2-20

Sequence Timer 4 Reference Source

0

n/a

5.11 S: Special Parameters

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

203