Bypass digital output terminal settings, Z2-31: safety open message selection, 14 z: bypass parameters – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 219

Advertising
background image

n

Z2-23 to Z2-26: Digital Output 7 to 10 Function Select

No.

Name

Setting Range

Default

Z2-23

Digital Output 7 Function Select

0 to 23; 99

7

Z2-24

Digital Output 8 Function Select

0 to 23; 99

10

Z2-25

Digital Output 9 Function Select

0 to 23; 99

12

Z2-26

Digital Output 10 Function Select

0 to 23; 99

15

n

Bypass Digital Output Terminal Settings

Table 5.31 Bypass Digital Output Terminal Settings

Setting

Function

0

Serial Comm Controlled

1

K1 Drive Input Contactor

2

K2 Drive Output Contactor

3

K3 Bypass Contactor

4

K4 Motor 1 Select

5

K5 Motor 2 Select

6

READY (Drive and Bypass)

7

RUN Active (Drive or Bypass)

8

Drive RUN Active

9

Bypass RUN Active

10

HAND Mode Active

11

OFF Mode Active

12

AUTO Mode Active

13

Drive Mode Selected

14

Bypass Mode Selected

Setting

Function

15

Drive or Bypass Fault Active

16

Drive Fault Active

17

Bypass Fault Active

18

Auto Transfer Active

19

Serial Run Command Active

20

Damper Actuator Output

21

ON Always

22

Loss of Load Detected

23

Run Verify

The digital output closes when the drive or bypass output

current exceeds 10% of the value set in E2-01.

The digital output opens when the drive or bypass output

current falls below 5% of the value set in E2-01.

99

Not Used (Through Mode)

This setting allows serial communications to control the

output.

n

Z2-31: Safety Open Message Selection

Sets the fault message displayed when an FB01 fault is triggered. This parameter also determines the text that is displayed on

the top line of the HOA keypad.

No.

Name

Setting Range

Default

Z2-31

Safety Open Message Selection

0 to 6

0

Setting 0: Safety Open

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR

ALM

ALM

BYP-SAFETY OPEN

BYP-FAULTED

DRV/BYP

FB01

Safety Open

RLY

FWD

UB-01= 0.0A

RLY

UB-02=10000101
UB-03=00001000

DRV/BYP

LSEQ

LREF

Setting 1: Fire Stat

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR

ALM

ALM

BYP-FIRE STAT

BYP-FAULTED

DRV/BYP

FB01

Fire Stat

RLY

FWD

UB-01= 0.0A

RLY

UB-02=10000101
UB-03=00001000

DRV/BYP

LSEQ

LREF

5.14 Z: Bypass Parameters

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

219