Use an optional soft starter on the line side of the bypass contactor to limit the current on the bypass circuit to motor FLA or

less. In this case, the bypass contactor is tested for a short-circuit combination rating of 65 kA or greater with the soft starter

and large enough to handle the motor FLA current.

n

Overload Relay

The adjustable thermal overload relay (OLR) provides overload protection for the motor in Drive and Bypass operating modes.

The bypass three-phase output power connection to the motor is made to the output terminals of the OLR. The OLR is set up

in the factory to be a manual reset device, requiring operator attention if an overload trip-out is experienced.

n

Control Power Transformer

A Control Power Transformer (CPT) is provided to power the bypass 120 Vac control circuit. The VA capacity is determined

by the control circuit and optional functions specified for the unit. The CPT primary is fused in both legs, the secondary is

fused when required by NEC (transformer VA and wire size dependent). One side of the transformer secondary is grounded

to the bypass enclosure.

n

Electronic Bypass Control Logic

Operating elements such as indicating LEDs, selector buttons, and control logic are incorporated into a PCB assembly to

eliminate the potential for loose wires after shipment.
The operating elements are located on PCB A3 and the control logic PCB A2 contains the control circuit field wiring terminal

blocks TB1 through TB5.

n

Drive/Bypass Logic Interlocks

The bypass 120 Vac logic circuit is interconnected with the drive multi-function digital input terminals and multi-function

digital output terminals to allow a single customer interface to control both drive and bypass circuits. These drive terminals

are not available for field connections. All field control connections are landed at terminal blocks TB1 through TB5 on control

logic PCB A2 and drive PCB A1.

1.5 Bypass Component Descriptions

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual