Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 166

Advertising
background image

Status

Drive Operation

Up (10)

Down (11)

Open

Open

Hold current frequency reference

Closed

Open

Increase frequency reference

Open

Closed

Decrease frequency reference

Closed

Closed

Hold current frequency reference

Note:

1. An oPE03 alarm occurs when only one of the Up/Down functions is programmed to a digital input.
2. An oPE03 alarm occurs when the Up/Down function is assigned to the terminals and a different digital input is programmed for the

Accel/decel ramp hold function. Refer to the Troubleshooting chapter in the User Manual packaged with the drive for more information

on alarms.

3. The Up/Down function can only be used for External reference 1. Consider this when using Up/Down and the external reference switching

command (H1-oo = 2).

Using the Up/Down Function with Frequency Reference Hold (d4-01)
• If the frequency reference hold function is disabled (d4-01 = 0), the Up/Down frequency reference will be reset to 0 when

the Run command is cleared or the power is cycled.

• When d4-01 = 1, the drive will save the frequency reference set by the Up/Down function. When the Run command or the

power is cycled, the drive will restart with the saved reference value. Close the Up or Down input without an active Run

command to reset the saved value.

Using the Up/Down Function with Frequency Reference Limits
The value for the lower frequency reference limit depends on the parameter d4-10 setting. This value can be set by an analog

input or parameter d2-02. When a Run command is applied, the lower limits function as follows:
• If the lower limit is set by d2-02 only, the drive accelerates to this limit as soon as a Run command is entered.
• If the lower limit is determined by an analog input only, the drive accelerates to the limit when both the Run command and

an Up or Down command are active. The drive will not start running if only the Run command is active.

• If the lower limit is set by both an analog input and d2-02, and the analog limit is higher than the d2-02 value, the drive

accelerates to the d2-02 value when a Run command is input. When the d2-02 value is reached, the drive accelerates to the

analog limit only if an Up or Down command is set.

Figure 5.18

shows an Up/Down function example with a lower frequency reference limit set by d2-02, and the frequency

reference hold function both enabled and disabled.

Accelerates to

lower limit

Output frequency

upper limit

Lower limit

FWD run/stop

Up command

Down command

Power supply

Same

frequency

d4-01 = 1

d4-01 = 0

ON

ON

ON

ON

ON

Hold
frequency
reset

Figure 5.18 Up/Down Command Operation

Setting 14: Fault Reset

When the drive detects a fault condition, the fault output contact closes, the drive output shuts off, and the motor coasts to

stop (specific stopping methods can be selected for some faults such as L1-04 for motor overheat). After removing the Run

command, clear the fault either by pressing the RESET key on the HOA keypad or closing a digital input configured as a Fault

Reset (H1-oo = 14).

Note:

Remove the Run command prior to resetting a fault. Fault Reset commands are ignored while the Run command is present.

5.7 H: Terminal Functions

166

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

Advertising