Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 424

Advertising
background image

Point

No.

Point

Type

Point Name

Factory

Default

(SI Units)

Engr. Units

(SI Units)

Slope

(SI Units)

Intercept

(SI Units)

On

Text

Off

Text

Z1000U

Parameter

91

LAO

CBL LOSS

FRQ

0

HZ

0.01

0

Z3-10

92

LAO

CBL LOSS

TMR

2

SEC

0.1

0

Z3-06

{93}

LDI

OK.FAULT

OK

1

0

FAULT

OK

UB-06 (Bit 2)

{94}

LDO

RESET

FAULT

NO

1

0

RESET

NO

{95}

LDI

DRV COMM

ERR

NO FLT

1

0

FAULT

NO FLT

{96}

LDO

EXTERNAL

FLT

OK

1

0

FAULT

OK

{97}

LDI

MF IN 5

MON

OFF

1

0

ON

OFF

UB-02 (Bit 6)

Bypass DI-7

{99}

LAI

ERROR

STATUS

0

1

0

<1> The number of decimal places in the value depends on the bypass model.
<2> Point LDI 18 displays both drive alarms and bypass alarms.
<3> Set Z2-02 to 22 (Run Enable) for point 35 to work properly.
<4> Disabled when Z3-12 is set to 0.

E.4 APOGEE FLN Point List Summary

424

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual