Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 424
Point
No.
Point
Type
Point Name
Factory
Default
(SI Units)
Engr. Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
Z1000U
Parameter
91
LAO
CBL LOSS
FRQ
0
HZ
0.01
0
–
–
Z3-10
92
LAO
CBL LOSS
TMR
2
SEC
0.1
0
–
–
Z3-06
{93}
LDI
OK.FAULT
OK
–
1
0
FAULT
OK
UB-06 (Bit 2)
{94}
LDO
RESET
FAULT
NO
–
1
0
RESET
NO
–
{95}
LDI
DRV COMM
ERR
NO FLT
–
1
0
FAULT
NO FLT
–
{96}
LDO
EXTERNAL
FLT
OK
–
1
0
FAULT
OK
–
{97}
LDI
MF IN 5
MON
OFF
–
1
0
ON
OFF
UB-02 (Bit 6)
Bypass DI-7
{99}
LAI
ERROR
STATUS
0
–
1
0
–
–
–
<1> The number of decimal places in the value depends on the bypass model.
<2> Point LDI 18 displays both drive alarms and bypass alarms.
<3> Set Z2-02 to 22 (Run Enable) for point 35 to work properly.
<4> Disabled when Z3-12 is set to 0.
E.4 APOGEE FLN Point List Summary
424
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual