Writing to Multiple Registers

Function code 10H allows the user to write multiple MEMOBUS/Modbus registers with one message. This process works

similar to reading registers, in that the address of the first register to be written and the data quantity are set in the command

message. The data to be written must be consecutive so that the register addresses are in order, starting from the specified

address in the command message. The data order must be high byte then lower byte.
The following table shows an example of a message where a forward operation has been set with a frequency reference of

60.0 Hz for the slave 1 drive.
If parameter values are changed using the Write command, an Enter command is necessary to save the data.

Refer to Enter

Command on page 376

for detailed descriptions.

Command Message

Response Message (normal)

Response Message (fault)

Slave Address

01H

Slave Address

01H

Slave Address

01H

Function Code

10H

Function Code

10H

Function Code

90H

Starting No.

Upper

00H

Starting No.

Upper

00H

Error Code

02H

Lower

01H

Lower

01H

CRC-16

Upper

CDH

Data Quantity

Upper

00H

Data Quantity

Upper

00H

Lower

C1H

Lower

02H

Lower

02H

Number of Bytes

04H

CRC-16

Upper

10H

Starting Data

Upper

00H

Lower

08H

Lower

01H

Next Data

Upper

02H

Lower

58H

CRC-16

Upper

63H

Lower

39H

Note:

Double the number of the data quantity for the number of bytes in the command message.

D.8 Message Examples

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual