No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b2-03

(018B)

DC Injection Braking

Time at Start

DCInj Time@Start

Sets DC Injection Braking time at start. Disabled when set to

0.00 seconds.

Default: 0.00 s

Min.: 0.00

Max.: 10.00

136

b2-04

(018C)

DC Injection Braking

Time at Stop

DCInj Time@Stop

Sets DC Injection Braking time at stop.

Default: 0.00 s

Min.: 0.00

Max.: 10.00

136

u

b3: Speed Search

No.

(Addr

Hex.)

Name

LCD Display

Description

Values

Page

b3-01

(0191)

Speed Search Selection

at Start

SpdSrch at Start

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

137

b3-03

(0193)

Speed Search

Deceleration Time

SpdSrch Dec Time

Sets output frequency reduction time during Speed Search.

Default: 2.0 s

Min.: 0.1

Max.: 10.0

137

b3-04

(0194)

V/f Gain during Speed

Search

SpdSrch V/f

Determines how much to lower the V/f ratio during Speed

Search.

Output voltage during Speed Search equals the V/f setting

multiplied by b3-04.

Default:

<1>

Min.: 10%

Max.: 100%

137

b3-05

(0195)

Speed Search Delay

Time

Search Delay

When using an external contactor on the output side, b3-05

delays executing Speed Search after a momentary power loss to

allow time for the contactor to close.

Default: 0.2 s

Min.: 0.0

Max.: 100.0

137

b3-06

(0196)

Output Current 1 during

Speed Search

Srch Im Lvl1

Sets the current injected to the motor at the beginning of Speed

Estimation Speed Search. Set as a coefficient for the motor rated

current.

Default:

<1>

Min.: 0.0

Max.: 2.0

138

b3-07

(0197)

Output Current 2 during

Speed Search (Speed

Estimation Type)

Srch Im Lvl2

Sets the amount of output current during Speed Estimation

Speed Search as a coefficient for the no-load current (output

current during Speed Search is automatically limited by the

drive rated current).

Increase this setting value in increments of 0.1 if the drive fails

to perform Speed Estimation.

Default: 1.0

Min.: 0.0

Max.: 5.0

138

b3-08

(198)

Current Control Gain

during Speed Search

(Speed Estimation

Type)

Srch ACR P Gain

Sets the proportional gain for the current controller during

Speed Search.

Default:

<1>

Min.: 0.00

Max.: 6.00

138

b3-09

(0199)

Current Control Integral

Time during Speed

Search (Speed

Estimation Type)

Srch ACR I Time

Sets the Integral Time for the current controller during Speed

Search.

Default: 2.0 ms

Min.: 0.0

Max.: 1000.0

138

b3-10

(019A)

Speed Search Detection

Compensation Gain

Srch Detect Comp

Sets the gain which is applied to the speed detected by Speed

Estimation Speed Search before the motor is reaccelerated.

Increase this setting if ov occurs when performing Speed Search

after a relatively long period of baseblock.

Default: 1.05

Min.: 1.00

Max.: 1.20

138

b3-11

(19B)

Speed Search Method

Switching Level (Speed

Estimation Type)

Srch Mthd Sw Lvl

Uses the amount of voltage remaining in the motor to

automatically switch the search method within the type of speed

measurement.

(208 Vac at 100% = 208 V;

480 V class at 100% = 480 V)

Default: 5.0%

Min.: 0.5

Max.: 100.0

138

b3-12

(019C)

Minimum Current

Detection Level during

Speed Search

Srch I Deadband

Sets the minimum current detection level during Speed Search.

Increase this setting value in increments of 0.1 if the drive fails

to perform Speed Estimation.

Default:

<1>

Min.: 2.0

Max.: 10.0

138

b3-14

(019E)

Bi-Directional Speed

Search Selection

Bidir Search Sel

0: Disabled

1: Enabled

0: Disabled (uses the direction of the frequency reference)

1: Enabled (drive detects which way the motor is rotating)

Default: 1

Range: 0, 1

139

b3-17

(01F0)

Speed Search Restart

Current Level

SrchRestart Lvl

Sets the Speed Search restart current level as a percentage of the

drive rated current.

Default: 150%

Min.: 0

Max.: 200

139

b3-18

(01F1)

Speed Search Restart

Detection Time

SrchRestart Time

Sets the time to detect Speed Search restart.

Default: 0.10 s

Min.: 0.00

Max.: 1.00

139