6.6 Operator Programming Errors

u

Operator Programming Error Codes, Causes, and Possible Solutions

A Programming Error (oPE) occurs when a contradictory parameter is set or an individual parameter is set to an inappropriate

value.
The drive will not operate until the parameter or parameters causing the problem are set correctly. An oPE, however, does not

trigger an alarm or fault output. If an oPE occurs, investigate the cause and refer to

Table 6.10

for the appropriate action. When

an oPE appears on the HOA keypad display, press the ENTER button to view U1-18 and see which parameter is causing the

oPE.

Table 6.10 oPE Codes, Causes, and Possible Solutions

HOA Keypad Display

Error Name

oPE01

Unit Capacity Setting Fault
Unit capacity and the value set to o2-04 do not match.

Cause

Possible Solutions

The drive model selection (o2-04) and the actual

capacity of the drive are not the same

Correct the value set to o2-04.

HOA Keypad Display

Error Name

oPE02

Parameter Range Setting Error
Use U1-18 to find parameters set outside the range.

Cause

Possible Solutions

Parameters were set outside the possible setting

range

Set parameters to the proper values.

Note:

When multiple errors occur simultaneously, other errors are given precedence over oPE02

HOA Keypad Display

Error Name

oPE03

Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function contact inputs H1-01 to H1-08.

Cause

Possible Solutions

• The same function is assigned to two

multi-function inputs

• Excludes “Not used” and “External Fault”

• Ensure all multi-function inputs are assigned to different functions.
• Re-enter the multi-function settings to ensure this does not occur.

The Up command was set but the Down command

was not, or vice versa (settings 10 vs. 11)

Properly set the functions that required for use in combination with other functions.

• Run/Stop command for a 2-wire sequence was

set (H1-oo = 42), but Forward/Reverse

command (H1-oo = 43) was not

• “Drive Enable” is set to multi-function input S1

or S2 (H1-01 = 6A or H1-02 = 6A)

Properly set the functions that required for use in combination with other functions.

Two of the following functions are set

simultaneously:
• Up/Down Command (10 vs. 11)
• Hold Accel/Decel Stop (A)
• Analog Frequency Reference Sample/Hold (1E)
• Offset Frequency 1, 2, 3 Calculations (44, 45,

46)

• Check if contradictory settings have simultaneously been assigned to the multi-function input

terminals.

• Correct setting errors.

The Up/Down command (10, 11) and PID control

(b5-01) are enabled simultaneously

Set b5-01 to 0 to disable control PID or disable the Up/Down command.

Settings for N.C. and N.O. input for the following

functions were selected simultaneously:
• External Search Command 1 and External

Search Command 2 (61 vs. 62)

• Fast Stop N.O. and Fast Stop N.C. (15 vs. 17)
• FWD Run Command (or REV) and FWD/REV

Run Command (2-wire) (40, 41 vs. 42, 43)

• Drive Enable (60 vs. 6A)

• Check if contradictory settings have simultaneously been assigned to the multi-function input

terminals.

• Correct setting errors.

6.6 Operator Programming Errors

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

259