Wiring diagram for multiple connections, Network termination, Ms/tp interface – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 365: C.3 connecting to a network

Advertising
background image

u

Wiring Diagram for Multiple Connections

Figure C.3

explains the wiring diagrams for multiple connections using BACnet communication.

n

MS/TP Interface

Figure C.3

shows typical “daisy-chain” RS-485 wiring. If the bypass is at the end of the network, the drain wire should not

be connected and should be insulated from touching other components or ground. Connect the drain wire to earth ground at

the controller only to avoid ground loops.

Note:

The isolated ground (IG5) connection is optional but strongly recommended to avoid noise issues. Yaskawa recommends using Belden

cable 3106A or equivalent for BACnet operation.

CONTROLLER

(customer-supplied)

1

2

3

4

+

-

SHLD

Bypass Drive

S1

OFF

TB3

SHLD

TXRX-

TXRX+

IG5

1

2

3

4

Bypass Drive

S1

OFF

TB3

SHLD

TXRX-

TXRX+

IG5

ON

1

2

3

4

Bypass Drive

S1

SHLD

TXRX-

TXRX+

IG5

Bypass
Control
Board A2

Bypass
Control
Board A2

Bypass
Control
Board A2

TB3

COMMON

Figure C.3 Connection Diagram for Multiple Connections

Note:

Turn on DIP switch S1 on the bypass that is located at the end of the network. If S1 is missing, then an external 120 ohm resistor must be

placed across terminals TXRX+ and TXRX-. All other slave devices must have this DIP switch set to the OFF position (or if S1 is missing,

no external resistor is used).

u

Network Termination

The two ends of the BACnet network line have to be terminated with a 120 ohm resistor between the TXRX+ and TXRX-

signals. The bypass has a built in termination resistor that can be enabled or disabled using DIP switch S1. If a bypass is located

at the end of a network line, enable the termination resistor by setting DIP switch S1 to the ON position. Disable the termination

resistor on all slaves that are not located at the network line end.

Note:

Some bypass controllers do not have DIP switch S1. If this is the case, then an external 120 ohm resistor must be placed across the

TXRX+ and TXRX- signals if the bypass controller is at the end of a network line.

C.3 Connecting to a Network

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

365

C

BACnet Communications

Advertising