If input phase rotation is reversed and this parameter is set to 2, an “FB16 – Inp Phase Rotation” fault will be displayed when

operation starts in Bypass Mode and the drive will coast to stop.
Controls the behavior of the bypass phase rotation detection when operating in Bypass Mode.

No.

Name

Setting Range

Default

Z1-52

Bypass Phase Rotation

0 to 2

1

Setting 0: Disabled
Setting 1: Alarm
Setting 2: Fault

u

Z2: Bypass Control Input/Output

n

Z2-01 to Z2-08: Digital Input 1 to 8 Function Select

No.

Name

Setting Range

Default

Z2-01

Digital Input 1 Function Select

0 to 36

21

Z2-02

Digital Input 2 Function Select

0 to 36

22

Z2-03

Digital Input 3 Function Select

0 to 36

23

Z2-04

Digital Input 4 Function Select

0 to 36

24

Z2-05

Digital Input 5 Function Select

0 to 36

25

Z2-06

Digital Input 6 Function Select

0 to 36

0

Z2-07

Digital Input 7 Function Select

0 to 36

0

Z2-08

Digital Input 8 Function Select

0 to 36

29

n

Bypass Digital Input Terminal Settings

Table 5.29 Bypass Digital Input Terminal Settings

Setting

Function

Page

0

<1>

Unused (Available for Serial Comms)

Note:

Multiple digital input terminals can

be programmed for “Unused

(Available for Serial Comms)”

(Z2-0o = 0). The drive will run only

when all digital inputs programmed

for “0” are active. This feature

applies to settings 0 and 22. Set all

other selections only once in

parameters Z2-01 to Z2-08.

217

3

DRV Multi-Function Input S3 (H1-03 Setting)

217

4

DRV Multi-Function Input S4 (H1-04 Setting)

217

5

DRV Multi-Function Input S5 (H1-05 Setting)

217

6

DRV Multi-Function Input S6 (H1-06 Setting)

217

7

DRV Multi-Function Input S7 (H1-07 Setting)

217

8

DRV Multi-Function Input S8 (H1-08 Setting)

217

21

Run (AUTO Mode)

217

22

<1>

Run Enable (Safety)

Note:

Multiple digital input terminals can

be programmed for “Run Enable

(Safety)” (Z2-0o = 22). The drive

will run only when all digital inputs

programmed for “22” are active.

This feature applies to settings 0 and

22. Set all other selections only once

in parameters Z2-01 to Z2-08.

217

Setting

Function

Page

23

Run Interlock (BAS)

217

24

Remote Transfer to Bypass

217

25

Smoke Purge Bypass Run to Destruction

217

26

Smoke Purge Drive Run to Destruction at Smoke

Purge Preset Speed

217

27

Motor OR Select

217

28

Motor AND Select

217

29

Motor 1 Overload Contact

217

30

Motor 2 Overload Contact

217

31

HAND Select

218

32

AUTO Select

218

33

DRIVE/BYPASS Select

218

34

Fault Reset

218

35

External Fault (EF0)

218

36

External Fault (EFB)

218

37

Run Reverse

218

<1> Can be set to multiple digital input parameters at the same time.

5.14 Z: Bypass Parameters

216

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual