Lcd display – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 112

Advertising
background image

u

LCD Display

5

3

1

2

6

]

4

]

7

Figure 4.2 LCD Display

Table 4.1 Display and Contents

No.

Name

Display

Content

1

Bypass/Drive Status Display

DRV

(not

blinking)

Displayed when In Drive Mode. The bypass will run in Drive Mode when a Run command is present.

DRV

(blinking)

Displayed when in Drive Mode, but a condition is making the bypass run in Bypass Mode.

BYP

(not

blinking)

Displayed when in Bypass Mode. The bypass will run in Bypass Mode when a Run command is

present.

In a three-contactor bypass, drive input contactor K1 is open and the drive will be powered down.

BYP

(blinking)

Displayed when in Bypass Mode with Drive Test Mode set. The bypass will run in Bypass Mode

when a Run command is present.

In a three-contactor bypass, drive input contactor K1 is closed and the drive is powered on.

2

Bypass Status Display

POWERUP Displayed when the bypass is powering up.

OFF

Displayed when no Run command is present and the safety circuit is closed.

WAIT_FOR

_RUN

Displayed when Run is requested, the safety circuit is closed, and the bypass is waiting for Run input.

SAFETY

OPEN

Displayed when the safety circuit input is open.

INTRLOCK

OPN

Displayed when a Run command is present, the safety circuit is closed, but the Interlock input is open.

PRE RUN

DRIVE

Displayed when the bypass is running in the Pre-Run State at the programmed frequency for the

programmed time.

RUN

DRIVE

Displayed when running in Drive Mode.

RUN

BYPASS

Displayed when running in Bypass Mode.

RMOT

XFER EN Displayed when running in Remote Transfer.

SMOK PRG

BYP

Displayed when running in Smoke Purge Bypass.

SMOK PRG

DRV

Displayed when running in Smoke Purge Drive.

4.2 Using the HOA Keypad

112

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual