Examples of sequence timers – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 201

Advertising
background image

Setting 0: Digital Output Only
Setting 1: Run
Setting 2: Run - PID Disable

n

S2-05/S2-10/S2-15/S2-20: Sequence Timers 1/2/3/4 Reference Source

Selects the frequency reference source used for running the drive when sequence timers 1 to 4 are active (only applicable when

S2-04/S2-09/S2-14/S2-19 are set to 1 or 2).

No.

Name

Setting Range

Default

S2-05

Sequence Timer 1 Reference Source

0 to 5

0

S2-10

Sequence Timer 2 Reference Source

0 to 5

0

S2-15

Sequence Timer 3 Reference Source

0 to 5

0

S2-20

Sequence Timer 4 Reference Source

0 to 5

0

Setting 0: Operator (d1-01)
Setting 1: Operator (d1-02)
Setting 2: Operator (d1-03)
Setting 3: Operator (d1-04)
Setting 4: Terminals
Setting 5: Serial Communication

u

Examples of Sequence Timers

n

Sequence Timer Example 1

Set the parameters as shown in

Table 5.24

to accomplish the timer sequencing in

Figure 5.50

.

Table 5.24 Sequence Timer Example 1 Parameter Settings

No.

Name

Setting

Comment

S2-01

Sequence Timer 1 Start Time

05:00

S2-02

Sequence Timer 1 Stop Time

15:00

S2-03

Sequence Timer 1 Day Selection

2

Mon to Fri

S2-04

Sequence Timer 1 Selection

1

Run

S2-05

Sequence Timer 1 Reference Source

0

Operator (d1-01)

S2-06

Sequence Timer 2 Start Time

19:00

S2-07

Sequence Timer 2 Stop Time

22:00

S2-08

Sequence Timer 2 Day Selection

2

Mon to Fri

S2-09

Sequence Timer 2 Selection

2

Run PID Disable

S2-10

Sequence Timer 2 Reference Source

1

Operator (d1-02)

S2-11

Sequence Timer 3 Start Time

06:00

S2-12

Sequence Timer 3 Stop Time

14:00

S2-13

Sequence Timer 3 Day Selection

3

Sat to Sun

S2-14

Sequence Timer 3 Selection

1

Run

S2-15

Sequence Timer 3 Reference Source

2

Operator (d1-03)

S2-16

Sequence Timer 4 Start Time

17:00

S2-17

Sequence Timer 4 Stop Time

21:00

S2-18

Sequence Timer 4 Day Selection

10

Sun

S2-19

Sequence Timer 4 Selection

0

Digital Output Only

S2-20

Sequence Timer 4 Reference Source

0

n/a

5.11 S: Special Parameters

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

201