HOA Keypad Display

Fault Name

External operator is not properly connected to the

drive

• Check the connection between the operator and the drive.
• Replace the cable if damaged.
• Turn off the drive input power and disconnect the operator. Reconnect the operator and reapply

drive input power.

HOA Keypad Display

Fault Name

ov

Control Circuit Overvoltage
Voltage in the control circuit has exceeded the overvoltage level.
• For 200 V class drives: approximately 450 V
• For 400 V class drives: approximately 900 V

Cause

Possible Solution

Ground fault in the output circuit causing the

capacitor to overcharge.

• Check the motor wiring for ground faults.
• Correct grounding shorts and reapply power.

Drive input power voltage is too high.

• Check the voltage.
• Lower drive input power voltage within the limits listed in the specifications.

The capacity of the input power supply is too

small.

Use a power supply that has at least twice the input capacity of the drive.

The input power supply repeatedly turned on and

off over a short period of time.

Implement countermeasures so that chattering does not occur for the input power supply.

An I/O terminal is loose.

Check the tightening torque of the I/O terminals.

Chattering in the magnetic contactor (MC)

installed between the drive output terminals and

the motor.

Implement countermeasures so that chattering does not occur for the MC.

There is a phase loss or an imbalance in the

interphase voltages of the input power supply.

Check the status of the input power supply and eliminate phase losses and imbalance.

HOA Keypad Display

Fault Name

SCF

Safety Circuit Fault
Safety Circuit Fault is detected.

Cause

Possible Solution

The safety circuit is damaged.

Replace either the control board or the entire drive. For instructions on replacing the control board,

contact Yaskawa or your nearest sales representative.

HOA Keypad Display

Fault Name

SEr

Too Many Speed Search Restarts
The number of Speed Search restarts exceeded the value set to b3-19.

Cause

Possible Solution

Parameters related to Speed Search are set to the

wrong values

• Reduce the detection compensation gain during Speed Search (b3-10).
• Increase the current level when attempting Speed Search (b3-17).
• Increase the detection time during Speed Search (b3-18).

The motor is coasting in the opposite direction of

the Run command

Set b3-14 to 1 to enable Bi-Directional Speed Search.

HOA Keypad Display

Fault Name

SoH

Snubber Discharge Resistor Overheat

Cause

Possible Solution

• The input power supply voltage is too high.
• The capacity of the power supply is too small.
• The distortion in the power supply is too large.

• Reduce the voltage to within the range in the power supply specifications.
• Increase the capacity of the power supply.
• Lower the impedance of the input power supply wiring.

The load was too large during repetitious

operation.

• Check the load conditions. Reduce the load.
• Increase the acceleration/deceleration time.

A phase loss occurred in the input power supply. Check the input power supply for phase loss or an imbalance in the interphase voltages.

HOA Keypad Display

Fault Name

SrC

Phase Order Detection Fault
The phase rotation direction for the input power supply changed.

6.4 Fault Detection