Bypass analog outputs – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 97

Advertising
background image

Type

Signal Name

Description

Specification

Digital Outputs

120 Vac

DO-1

Digital Output 1

(Factory use only) 120 Vac, 66 VA sealed, 1650 inrush

DO-2

Digital Output 2

DO-3

Digital Output 3

DO-4

Digital Output 4

DO-5

Digital Output 5

Digital Outputs

DO-6

Digital Output 6

Relay, dry contact form C, 30 Vdc or 120 Vac,

DO-6 (factory use only), 3.7 Amp 360 VA,

DO-7 to DO-10 for customer use, 2 Amp

DO-7

Digital Output 7

DO-8

Digital Output 8

DO-9

Digital Output 9

DO-10

Digital Output 10

Table 3.8

lists the available control circuit input terminals on the drive. Text in parenthesis indicates the default setting for

each multi-function input.
The drive control circuit terminals on Terminal Board A1 are arranged as shown in

Figure 3.19

.

E(G) IG R+ R- S+ S-

S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP

V+ AC A1 A2 A3 FM AM AC

24V

RP AC

M1 M2 M3 M4

MD ME MF

MA MB MC

E(G) IG R+ R- S+ S-

S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP

V+ AC A1 A2 A3 FM AM AC

24V

RP AC

M1 M2 M3 M4

MD ME MF

MA MB MC

TB5

Figure 3.19 Control Circuit Terminal Arrangement

Table 3.8 Control Circuit Input Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Page

Analog Inputs

+V

Power supply for analog inputs

10.5 Vdc (max allowable current 20 mA)

208

24 V +24 Vdc transducer power supply for customer

use

150 mA maximum capacity

A1

Multi-function analog input 1

(Frequency reference bias)

• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-01.

208

174

A2

Multi-function analog input 2

(Frequency reference bias)

• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-09.

208

208

176

A3

Multi-function analog input 3

(Aux reference 1)

• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-05.

208

AC

Frequency reference common

0 V

208

E (G) Ground for shielded lines

u

Bypass Analog Outputs

There are two analog outputs that can be configured for a signal level of 0 to 10 Vdc or 4 to 20 mA. The signal level is controlled

by the position of jumpers J2 and J3 on Control PCB A2 and by the values set to drive parameters H4-07 and H4-08.

3.5 Control Circuit Wiring

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

97

3

Electrical Installation