Bacnet configuration, C.1 bacnet configuration – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 362

Advertising
background image

C.1 BACnet Configuration

The bypass system can be monitored and controlled by a controller on a Building Automation and Control network (BACnet)

using RS-485 technology and MS/TP (Master-Slave/Token-Passing) protocol. The bypass conforms to the BACnet application

specific controller (B-ASC) device profile. BACnet MS/TP connection is made to the bypass controller. Parameters and

monitors in both the drive and the bypass controller are made accessible from this one connection.
Up to 127 bypasses can communicate on a single BACnet MS/TP network. If more bypasses or BACnet devices are required,

then a BACnet router is required to allow another MS/TP network to be available with up to another 127 bypasses.
The BACnet node address is configurable by a parameter in the bypass. This defines the physical address of the bypass on the

MS/TP network. In addition, both the Device Object instance ID and the Device Object Name are configurable. These allow

the bypass to have a virtual address, and simplify the controller configuration.
Once the addressing is set, a controller can initiate communication to the bypass. The bypass will perform the specified function

and then send a response back to the controller. The bypass will usually respond immediately, but may delay its response until

it gets the token for commands that may take extra local processing time.

BACnet

Workstation

MS/TP

BACnet over Ethernet

Router

Z1000U

Bypass

Z1000U

Bypass

Z1000U

Bypass

MS/TP

Router

Z1000U

Bypass

Z1000U

Bypass

Z1000U

Bypass

Figure C.1 Connecting Multiple Bypasses to a BACnet Workstation

C.1 BACnet Configuration

362

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

Advertising