oPE02 Error Occurs When Lowering the Motor Rated Current Setting

Cause

Possible Solutions

Motor rated current and the motor no-load current

setting in the drive are incorrect.

• The user is trying to set the motor rated current in E2-01 to a value lower than the no-load

current set in E2-03.

• Make sure that value set in E2-01 is higher than E2-03.
• If it is necessary to set E2-01 lower than E2-03, first lower the value set to E2-03, then change

the setting in E2-01 as needed.

u

Motor Stalls during Acceleration or Acceleration Time is Too Long

Cause

Possible Solutions

Torque limit has been reached or current suppression

keeps the drive from accelerating.

Take the following steps to resolve the problem:
• Reduce the load.
• Increase motor capacity.

Note:

Although the drive has a Stall Prevention function and a Torque Compensation

Limit function, accelerating too quickly or trying to drive an excessively large

load can exceed the capabilities of the motor.

Load is too heavy.

Torque limit is not set properly.

Check the torque limit setting.

Frequency reference is too low.

• Check the maximum output frequency (E1-04).
• Increase E1-04 if it is set too low.
Check U1-01 for proper frequency reference.
Check if a frequency reference signal switch has been set to one of the multi-function input

terminals.
Check for low gain level set to terminals A1, A2, or A3 (H3-03, H3-11, H3-07).

Load is too heavy.

• Reduce the load so that the output current remains within the motor rated current.
• In extruder and mixer applications, the load will sometimes increase as the temperature drops.
• Increase the acceleration time.
• Check if the mechanical brake is fully releasing as it should.

Acceleration time has been set too long.

Check if the acceleration time parameter has been set too long (C1-01).

Motor characteristics and drive parameter settings are

incompatible with one another.

• Set the correct V/f pattern so that it matches the characteristics of the motor being used.
• Check the V/f pattern set to E1-03.
• Execute Rotational Auto-Tuning.

Incorrect frequency reference setting.

• Check the multi-function analog input settings. Multi-function analog input terminal A1, A2,

or A3 is set for frequency gain (H3-02, H3-10, or H3-06 is set to “1”), but there is no voltage

or current input provided.

• Make sure H3-02, H3-10, and H3-06 are set to the proper values.
• See if the analog input value is set to the right value (U1-13 to U1-15).

The Stall Prevention level during acceleration and

deceleration set too low.

• Check the Stall Prevention level during acceleration (L3-02).
• If L3-02 is set too low, acceleration may be taking too long.
• Increase L3-02.

The Stall Prevention level during run has been set too

low.

• Check the Stall Prevention level during run (L3-06).
• If L3-06 is set too low, speed will drop as the drive outputs torque.
• Increase the setting value.

u

Drive Frequency Reference Differs from the Controller Frequency Reference Command

Cause

Possible Solutions

The analog input gain and bias for the frequency

reference input are set to incorrect values.

• Check the gain and bias settings for the analog inputs that are used to set the frequency reference.

Check parameters H3-03 and H3-04 for input A1, check parameters H3-11, and H3-12 for input

A2, and check parameters H3-07 and H3-08 for input A3.

• Set these parameters to the appropriate values.

A frequency bias signal is being entered via analog

input terminals A1 to A3.

• If more than one of multi-function analog inputs A1 to A3 is set for frequency reference bias

(H3-02, H3-10, or H3-06 is set to “0”), then the sum of all signals builds the frequency reference.

• Make sure that H3-02, H3-10, and H3-06 are set appropriately.
• Check the input level set for terminals A1 to A3 (U1-13 to U1-15).

6.9 Troubleshooting without Fault Display