B8: energy saving – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 315

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b5-34

(019F) PID Output Lower Limit PID Out Low Lim

Sets the minimum output possible from the PID controller as a

percentage of the maximum output frequency.

Default: 0.0%

Min.: -100.0

Max.: 100.0

150

b5-35

(01A0) PID Input Limit

PID Input Limit

Limits the PID control input (deviation signal) as a percentage

of the maximum output frequency. Acts as a bipolar limit.

Default:

1000.0%

Min.: 0.0

Max.: 1000.0

150

b5-36

(01A1)

PID Feedback High

Detection Level

Fb High Det Lvl

Sets the PID feedback high detection level as a percentage of

the maximum output frequency.

Default: 100%

Min.: 0

Max.: 100

149

b5-37

(01A2)

PID Feedback High

Detection Time

Fb High Dly Time

Sets the PID feedback high level detection delay time.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

149

b5-38

(01FE)

PID Setpoint User

Display

PID UsrDspMaxVal

Sets the display value of U5-01 and U5-04 when the maximum

frequency is output.

Default:

<2>

Min.: 1

Max.: 60000

150

b5-39

(01FF)

PID Setpoint Display

Digits

PID UsrDspDigits

0: No Dec (XXXXX)

1: 1 Dec (XXXX.X)

2: 2 Dec (XXX.XX)

3: 3 Dec (XX.XXX)

0: No decimal places

1: One decimal place

2: Two decimal places

3: Three decimal places

Default:

<2>

Range: 0 to 3

150

b5-40

(017F)

Frequency Reference

Monitor Content during

PID

Fref Mon Sel@PID

0: Fref Mon w PID

1: Fref Mon w/o PID

0: Display the frequency reference (U1-01) after PID

compensation has been added.

1: Display the frequency reference (U1-01) before PID

compensation has been added.

Default: 0

Range: 0, 1

151

b5-46

(0165)

PID Setpoint Monitor

Unit Selection

PID Unit Sel

0: WC

1: PSI

2: GPM

3: °F

4: CFM

5: CMH

6: LPH

7: LPS

8: bar

9: Pa

10: °C

11: Mtr

12: Ft

13: LPM

14: CMM

0: WC (Inch of water)

1: PSI (Pounds per square inch)

2: GPM (Gallons per minute)

3: F (Degrees Fahrenheit)

4: CFM (Cubic feet per minute)

5: CMH (Cubic meters per hour)

6: LPH (Liters per hour)

7: LPS (Liters per second)

8: Bar (Bar)

9: Pa (Pascal)

10: C (Degrees Celsius)

11: Mtr (Meters)

12: Ft (Feet)

13: LPM (Liters per minute)

14: CMM (Cubic meters per minute)

Default: 0

Range: 0 to 14

151

b5-47

(017D)

Reverse Operation

Selection 2 by PID

Output

Output Rev Sel2

0: 0 limit

1: Reverse

Reverse operation selection when b5-01 = 3

0: Reverse Disabled

1: Reverse Enabled

Default: 1

Range: 0, 1

151

<1> Internally limited to the value of b5-38. Changing b5-20, b5-38, and b5-39 will not automatically update the value of this parameter.
<2> Default setting is dependent on parameter b5-20, PID Setpoint Scaling.

u

b8: Energy Saving

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b8-01

(01CC)

Energy Saving Control

Selection

Energy Save Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

B.3 b: Application

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

315

B

Parameter List