H2 Multi-Function Digital Output Settings

H2-oo

Setting

Function

LCD Display

Description

Page

37

During frequency output During RUN 2

Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial

Excitation is being performed.

Closed: Drive is running the motor (not in a baseblock state and DC Injection is

not being performed).

173

38

Drive Enable

Drive Enable

Closed: The digital output set for “Drive Enable” closes.

174

39

Energy pulse output

Energy Pulse Out

Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate

the kWh count.

174

3A

Regenerated power

pulse output

RegEn Pulse Out

Outputs a pulse to indicate the regenerated power.

174

3D

During speed search

During SpdSrch

Closed: Speed Search is being executed.

174

3E

PID feedback low

PID Feedback Low

Closed: PID feedback level is too low.

3F

PID feedback high

PID FeedbackHigh

Closed: The PID feedback level is too high.

4C

During fast stop

During Fast Stop

Closed: A Fast Stop command has been entered from the operator or input

terminals.

174

4D

oH Pre-alarm time limit OH Pre-Alarm

Closed: oH pre-alarm time limit has passed.

174

60

Internal cooling fan

alarm

Fan Alrm Det

Closed: Internal cooling fan alarm

174

64

During Commercial

Power Operation

CommerclPwr Mode Closed: Operating on commercial power.

174

100 to

164

Function 0 to 64 with

inverse output

Note: A prefix of "!" is

added to represent

inverse functions on the

LCD keypad display.

Example: “!Zero speed”

Inverts the output switching of the multi-function output functions.

Set the last two digits of 1oo to reverse the output signal of that specific function.

174

u

H3: Multi-Function Analog Inputs

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H3-01

(0410)

Terminal A1 Signal

Level Selection

Term A1 Level

0: 0-10V,

(LowLim=0)

1: 0-10V, (BipolRef)

2: 4-20 mA

3: 0-20 mA

0: 0 to 10 V with zero limit

1: 0 to 10 V without zero limit

2: 4-20 mA

3: 0-20 mA

Note:

Use jumper switch S1 to set input terminal A1

for current or voltage.

Default: 0

Range: 0 to 3

174

H3-02

(0434)

Terminal A1 Function

Selection

Term A1 FuncSel

Sets the function of terminal A1.

Default: 0

Range: 0 to 26

175

H3-03

(0411)

Terminal A1 Gain

Setting

Terminal A1 Gain

Sets the level of the input value selected in H3-02 when 10 V

is input at terminal A1.

Default: 100.0%

Min.: -999.9

Max.: 999.9

175

H3-04

(0412)

Terminal A1 Bias

Setting

Terminal A1 Bias

Sets the level of the input value selected in H3-02 when 0 V is

input at terminal A1.

Default: 0.0%

Min.: -999.9

Max.: 999.9

175

H3-05

(0413)

Terminal A3 Signal

Level Selection

Term A3 Signal

0: 0-10V (LowLim=0)

1: 0-10V, (BipolRef)

2: 4-20mA

3: 0-20mA

0: 0 to 10 V

1: -10 to 10 V

2: 4 to 20 mA

3: 0 to 20 mA

Note:

Use jumper switch S1 to set input terminal A3

for current or voltage input signal.

Default: 0

Range: 0 to 3

176

H3-06

(0414)

Terminal A3 Function

Selection

Terminal A3 Sel

Sets the function of terminal A3.

Default: 2

Range: 0 to 26

176

H3-07

(0415)

Terminal A3 Gain

Setting

Terminal A3 Gain

Sets the level of the input value selected in H3-06 when 10 V

is input at terminal A3.

Default: 100.0%

Min.: -999.9

Max.: 999.9

176

B.8 H Parameters: Multi-Function Terminals

326

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual