Refer to, Figure 3.9, Enable the internal emc filter – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 89

Advertising
background image

Figure 3.9 Ground Wiring for Multiple Bypass Units

n

Enable the Internal EMC Filter

If EMC is a concern and the network is grounded symmetrically, install the SW screw to the ON position. Installing the SW

screw enables the internal EMC filter (Drives are shipped with the SW screw installed at the OFF position).

DANGER! Electrical Shock Hazard. Do not touch SW screw while power is applied to the drive. Failure to comply will result in death or

serious injury.

WARNING! Electrical Shock Hazard. Connect the ground cable correctly. Failure to comply may result in death or serious injury.

NOTICE: When disabling the internal EMC filter, move the screws from ON to OFF and then tighten to the specified torque. Completely

removing the screws or tightening the screws to an incorrect torque may cause drive failure.

Note:

For floating, impedance grounded, or asymmetrically grounded networks, disconnect the internal EMC filter by moving the SW screw to

the OFF position.

Table 3.6

shows asymmetrical grounded networks. Asymmetrical networks require first moving the SW screw to disconnect

the internal ground connection. (Drives are shipped with the SW screw installed at the OFF position.)

Table 3.6 Asymmetrical Grounded Network

Grounded at the corner of the delta

L1

L2

L3

Grounded at the middle of the side

L1

L2

L3

Single-phase, grounded at the end point

L1

N

3.4 Input and Output Power Wiring Connections

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

89

3

Electrical Installation

Advertising