Alarm Outputs for Maintenance Monitors

An output can be set up to inform the user when a specific components has neared its expected performance life.
When one of multi-function digital output terminals has been assigned the maintenance monitor function (H2-oo = 2F), the

terminal will close when the cooling fan, DC bus capacitors, or DC bus pre-charge relay reach 90% of the expected performance

life, or when the IGBTs have reached 50% of their expected performance life. Additionally the HOA keypad will display an

alarm like shown in

Table 7.5

to indicate the specific components that may need maintenance.

Table 7.5 Maintenance Alarms

HOA Keypad Alarm Display

Function

Corrective Action

LT-1

The cooling fans have reached 90% of their designated

life time.

Replace the cooling fan.

LT-2

The DC bus capacitors have reached 90% of their

designated life time.

Contact a Yaskawa representative or the

nearest Yaskawa sales office on

possible drive replacement.

LT-3

The DC bus charge circuit has reached 90% of its

designated life time.

Contact a Yaskawa representative or the

nearest Yaskawa sales office on

possible drive replacement.

7.3 Periodic Maintenance

282