Z2: bypass control input/output – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 353

Advertising
background image

u

Z2: Bypass Control Input/Output

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

Z2-01

(8563) Digital Input 1 Function

Select

DI-1 Func Sel

0: Unused (Available for Serial Comms)

3: DRV Multi-Function Input S3 (H1-03 Setting)

4: DRV Multi-Function Input S4 (H1-04 Setting)

5: DRV Multi-Function Input S5 (H1-05 Setting)

6: DRV Multi-Function Input S6 (H1-06 Setting)

7: DRV Multi-Function Input S7 (H1-07 Setting)

7: DRV Multi-Function Input S8 (H1-08 Setting)

21: Run (AUTO Mode)

22: Run Enable (Safety)

23: Run Interlock (BAS)

24: Remote Transfer to Bypass

25: Smoke Purge Bypass Run to Destruction

26: Smoke Purge Drive Run to Destruction at Smoke Purge

Preset Speed. Bypass controller will stay in this state even if the

drive faults or is unavailable.

27: Motor OR Select (2-Motor OR function; 0/1 for Motor 1/2.

Behavior defined by Z1-11)

28: Motor AND Select (2-Motor AND function; 0/1 for 1/2

motor. If 1 motor, then look to Motor OR input for selected motor.

Behavior defined by Z1-11)

29: Motor 1 Overload Contact. When input is open, declare an

OL Fault, issue an EF0 fault to the drive, delay per EF0 Fault

Delay Time (Z1-30), and open Drive Output (K2) and Bypass

(K3) contactors.

30: Motor 2 Overload Contact. When input is open, declare an

OL Fault, issue an EF0 fault to the drive, delay per EF0 Fault

Delay Time (Z130), and open Drive Output (K2) and Bypass

(K3) contactors.

31: HAND Select

32: AUTO Select

33: DRIVE/BYPASS Select (0/1 for Drive/Bypass)

34: Fault Reset

35: External Fault (EF0)

36: External Fault (EFB)

37: Run Reverse

Default: 21

Range: 0 to 37

216

Z2-02

(8564) Digital Input 2 Function

Select

DI-2 Func Sel

Default: 22

Range: 0 to 37

216

Z2-03

(8565) Digital Input 3 Function

Select

DI-3 Func Sel

Default: 23

Range: 0 to 37

216

Z2-04

(8566) Digital Input 4 Function

Select

DI-4 Func Sel

Default: 24

Range: 0 to 37

216

Z2-05

(8567) Digital Input 5 Function

Select

DI-5 Func Sel

Default: 25

Range: 0 to 37

216

Z2-06

(8568) Digital Input 6 Function

Select

DI-6 Func Sel

Default: 0

Range: 0 to 37

216

Z2-07

(8569)

Digital Input 7 Function

Select

DI-7 Func Sel

Default: 0

Range: 0 to 37

216

Z2-08

(856A) Digital Input 8 Function

Select

DI-8 Func Sel

Default: 29

Range: 0 to 37

216

Z2-09

(856B) Digital Input 1 Invert

Select

DI-1 Invert

0: Normal

1: Inverted

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

218

Z2-10

(856C) Digital Input 2 Invert

Select

DI-2 Invert

0: Normal

1: Inverted

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

218

Z2-11

(856D) Digital Input 3 Invert

Select

DI-3 Invert

0: Normal

1: Inverted

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

218

Z2-12

(856E) Digital Input 4 Invert

Select

DI-4 Invert

0: Normal

1: Inverted

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

218

Z2-13

(856F) Digital Input 5 Invert

Select

DI-5 Invert

0: Normal

1: Inverted

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

218

Z2-14

(8570) Digital Input 6 Invert

Select

DI-6 Invert

0: Normal

1: Inverted

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

218

Z2-15

(8571) Digital Input 7 Invert

Select

DI-7 Invert

0: Normal

1: Inverted

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

218

B.15 Z: Bypass Parameters

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

353

B

Parameter List