Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 221

Advertising
background image

No.

Name

Setting Range

Default

Z3-02

Serial Communications Node Select

0 to 127

1

n

Z3-03: Serial Communications Baud Rate Select

Selects the bypass serial communications speed.

No.

Name

Setting Range

Default

Z3-03

Serial Communications Baud Rate Select

0 to 8

3

Setting 0: 1200 bps
Setting 1: 2400 bps
Setting 2: 4800 bps
Setting 3: 9600 bps
Setting 4: 19200 bps
Setting 5: 38400 bps
Setting 6: 57600 bps
Setting 7: 76800 bps
Setting 8: 115200 bps

n

Z3-04: Serial Communications Parity Select

Selects the bypass serial communications parity. This setting is ignored when BACnet protocol is selected.

No.

Name

Setting Range

Default

Z3-04

Serial Communications Parity Select

0 to 2

0

Setting 0: No Parity
Setting 1: Even Parity
Setting 2: Odd Parity

n

Z3-05: Serial Communications Fault Select

Selects the action to take when a serial communications fault is detected. A serial communications fault is detected when after

last communicating, no communications occurs within the time set to Z3-06.

No.

Name

Setting Range

Default

Z3-05

Serial Communications Fault Select

0 to 4

1

Setting 0: Ignore
Setting 1: Alarm Only
Setting 2: Fault with EF0

An EF0 fault will be sent to the drive.

Setting 3: Fault with EF0 and Open Contactors

An EF0 fault will be sent to the drive and the bypass contactor (K3) will be opened.

Setting 4: Alarm and run at preset speed set in Z3-10

Display AL14 alarm on operator.

n

Z3-06: Serial Communications Fault Time Select

Sets the time allowed to elapse since receiving serial communications before triggering a communications fault.
A value of 0.0 means to never time out.

No.

Name

Setting Range

Default

Z3-06

Serial Communications Fault Time Select

0.0 s to 99.9 s

2.0 s

n

Z3-07: Serial Communications Receive to Transmit Wait Time

Sets the time to delay a serial communications response to a serial communications command.

5.14 Z: Bypass Parameters

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

221

5

Programming