H1 Multi-Function Digital Input Selections

H1-oo

Setting

Function

LCD Display

Description

Page

10

Up command

Up Command 1

The drive accelerates when the Up command terminal closes, and decelerates when

the Down command closes. When both terminals are closed or both are open, the

drive holds the frequency reference. The Up and Down commands must always

be used in conjunction with one another.

165

11

Down command

Down Command 1

The drive accelerates when the Up command terminal closes, and decelerates when

the Down command closes. When both terminals are closed or both are open, the

drive holds the frequency reference. The Up and Down commands must always

be used in conjunction with one another.

165

14

Fault reset

Fault Reset

Closed: Resets faults if the cause is cleared and the Run command is removed.

166

15

Fast Stop (N.O.)

Fast-Stop N.O.

Closed: Decelerates at the Fast Stop time set to C1-09.

17

Fast Stop (N.C.)

Fast-Stop N.C.

Open: Decelerates to stop at the Fast Stop time set to C1-09.

19

PID disable

PID Disable

Open: PID control enabled

Closed: PID control disabled

167

1B

Program lockout

Program Lockout

Open: Parameters cannot be edited (except for U1-01 if the reference source is

assigned to the HOA keypad).

Closed: Parameters can be edited and saved.

1E

Reference sample hold

Ref Sample Hold

Closed: Samples the analog frequency reference and operates the drive at that

speed.

24

External fault

NO/ Always Det,

Coast to Stop

N.O., Always detected, coast to stop

167

30

PID integral reset

PID Intgrl Reset

Closed: Resets the PID control integral value.

31

PID integral hold

PID Intgrl Hold

Open: Performs integral operation.

Closed: Maintains the current PID control integral value.

34

PID soft starter cancel

PID SFS Cancel

Open: PID soft starter is enabled.

Closed: Disables the PID soft starter b5-17.

35

PID input level selection PID Input Invert

Closed: Inverts the PID input signal.

40

Forward run command

(2-Wire sequence)

FwdRun 2Wire Seq

Open: Stop

Closed: Forward run

Note:

Cannot be set together with settings 42 or 43.

41

Reverse run command

(2-Wire sequence)

RevRun 2WireSeq

Open: Stop

Closed: Reverse run

Note:

Cannot be set together with settings 42 or 43.

42

Run command

(2-Wire sequence 2)

Run/Stp 2WireSeq

Open: Stop

Closed: Run

Note:

Cannot be set together with settings 40 or 41.

43

FWD/REV command

(2-Wire sequence 2)

FWD/REV 2WireSeq

Open: Forward

Closed: Reverse

Note:

Determines motor direction, but does not issue a Run command.

Cannot be set together with settings 40 or 41.

44

Offset frequency 1

Offset Freq 1

Closed: Adds d7-01 to the frequency reference.

45

Offset frequency 2

Offset Freq 2

Closed: Adds d7-02 to the frequency reference.

46

Offset frequency 3

Offset Freq 3

Closed: Adds d7-03 to the frequency reference.

50

Motor Pre-Heat 2

Motor Preheat 2

Closed: Triggers Motor Pre-Heat 2.

51

Sequence Timer Disable SeqTimer Disable

Closed: Drive ignores sequence timers and runs normally.

60

Motor pre-heat 1

DCInj Activate

Closed: Triggers Motor pre-heat 1.

167

61

External Speed Search

command 1

Speed Search 1

Closed: Activates Current Detection Speed Search from the maximum output

frequency (E1-04).

62

External Speed Search

command 2

Speed Search 2

Closed: Activates Current Detection Speed Search from the frequency reference.

6A

Drive enable

Drive Enable

Open: Drive disabled. If this input is opened during run, the drive will stop as

specified by b1-03.

Closed: Ready for operation.

B.8 H Parameters: Multi-Function Terminals

324

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual