Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 237

Advertising
background image

HOA Keypad Display

Fault Name

Cause

Possible Solution

• The capacity of the power supply is too small.
• The distortion in the power supply is too large.

• Increase the capacity of the power supply.
• Lower the impedance of the input power supply wiring.

A phase loss occurred in the input power supply. Check the input power supply for phase loss or an imbalance in the interphase voltages.

HOA Keypad Display

Fault Name

EF0

Option Card External Fault
An external fault condition is present.

Cause

Possible Solution

An external fault was received from the PLC and

F6-03 is set to a value other than 3

• Remove the cause of the external fault.
• Remove the external fault input from the PLC.

Problem with the PLC program

Check the PLC program and correct problems.

HOA Keypad Display

Fault Name

EF1

External Fault (input terminal S1)
External fault at multi-function input terminal S1.

EF2

External Fault (input terminal S2)
External fault at multi-function input terminal S2.

EF3

External Fault (input terminal S3)
External fault at multi-function input terminal S3.

EF4

External Fault (input terminal S4)
External fault at multi-function input terminal S4.

EF5

External Fault (input terminal S5)
External fault at multi-function input terminal S5.

EF6

External Fault (input terminal S6)
External fault at multi-function input terminal S6.

EF7

External Fault (input terminal S7)
External fault at multi-function input terminal S7.

EF8

External Fault (input terminal S8)
External fault at multi-function input terminal S8.

Cause

Possible Solution

An external device tripped an alarm function

• Properly connect the signal lines to the terminals assigned for external fault detection

(H1-oo = 24).

• Reconnect the signal line.

Multi-function contact input setting is incorrect

• Check for unused terminals set for H1-oo = 24 (External Fault).
• Change the terminal settings.

HOA Keypad Display

Fault Name

Err

EEPROM Write Error

Data cannot be written to the EEPROM

Cause

Possible Solution

Noise has corrupted data while writing to the

EEPROM

• Press “ENTER” on the HOA keypad.
• Correct the parameter setting.
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a

Yaskawa representative for instructions on replacing the control board.

Hardware problem

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

FAn

Internal Fan Fault
Fan or magnetic contactor failure

Cause

Possible Solution

6.4 Fault Detection

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

237

6

Diagnostics & Troubleshooting

Advertising