L8-06: Input Phase Loss Detection Level

Sets the Input Phase Loss Detection (PF) Level.
Triggers PF fault when there is an imbalance larger than the value set to L8-06 in the drive input power voltage.
Detection Level = 100% = Voltage Class ×

No.

Name

Setting Range

Default

L8-06

Input Phase Loss Detection Level

0.0 to 50.0%

Det. by o2-04

n

L8-07: Output Phase Loss Protection Selection

Enables or disables the output phase loss detection triggered when the output current falls below 5% of the drive rated current.

Note:

Output phase loss detection may mistakenly trigger if the motor rated current is very small compared to drive rating. Disable L8-07 in such

cases.

No.

Name

Setting Range

Default

L8-07

Output Phase Loss Protection Selection

0 to 2

1

Setting 0: Disabled
Setting 1: Fault when One Phase Is Lost

An output phase loss fault (LF) is triggered and the motor coasts to stop when one output phase is lost.

Setting 2: Fault when Two Phases Are Lost

An output phase loss fault (LF) is triggered and the motor coasts to stop when two or more output phases are lost.

n

L8-09: Output Ground Fault Detection Selection

Enables or disables the output ground fault detection.

No.

Name

Setting Range

Default

L8-09

Output Ground Fault Detection Selection

0, 1

Determined by

o2-04

Setting 0: Disabled

Ground faults are not detected.

Setting 1: Enabled

A ground fault (GF) is triggered when high leakage current or a ground short circuit occurs in one or two output phases.

n

L8-38: Carrier Frequency Reduction Selection

Selects operation of the carrier frequency reduction function. Reduces the carrier frequency when the output current exceeds

a certain level. This temporarily increases the overload capability, allowing the drive to run through transient load peaks

without tripping.

No.

Name

Setting Range

Default

L8-38

Carrier Frequency Reduction Selection

0 to 2

Det. by o2-04

Setting 0: Disabled

No carrier frequency reduction at high current.

Setting 1: Enabled for Output Frequencies below 6 Hz

The carrier frequency is reduced at speeds below 6 Hz when the current exceeds 100% of the drive rated current. The drive

returns to the normal carrier frequency when the current falls below 88% or the output frequency exceeds 7 Hz.

Setting 2: Enabled for Entire Frequency Range

The carrier frequency is reduced at the following speeds:
• Below 6 Hz when the current exceeds 100% of the drive rated current.
• Above 7 Hz when the current exceeds 112% of the drive rated current.
The drive uses the delay time set in parameter L8-40 and a hysteresis of 12% when switching the carrier frequency back to

the set value.

5.8 L: Protection Functions