U3: fault history – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 345

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U2-14

(008D)

Cumulative Operation

Time at Previous Fault Elapsed time

Displays the cumulative operation time at the previous fault.

No signal output

available

1 h

U2-15

(07E0)

Soft Starter Speed

Reference at Previous

Fault

SFS Output

Displays the speed reference for the soft starter at the previous

fault.

No signal output

available

0.01 Hz

U2-16

(07E1)

Motor q-Axis Current at

Previous Fault

Motor Iq Current

Displays the q-axis current for the motor at the previous fault.

No signal output

available

0.10%

U2-20

(008E)

Heatsink Temperature at

Previous Fault

Actual Fin Temp

Displays the temperature of the heatsink when the most recent

fault occurred.

No signal output

available

1 °C

U2-30

(3008)

Date Year at Previous

Fault

Date Year YYYY

Displays the year when the most recent fault occurred.

No signal output

available

U2-31

(3009)

Date Month and Day at

Previous Fault

Date Mo Day MMDD Displays the date and day when the most recent fault occurred. No signal output

available

U2-32

(300A)

Time Hours and Minutes

at Previous Fault

Time Hr Min HHMM Displays the time when the most recent fault occurred.

No signal output

available

U2-50

(085C) Input Power Supply

Power Supply Sts

Information at Previous Fault Displays the input power supply

information at the previous fault. Displayed as in U1-72.

No signal output

available

U2-54

(0843)

Power Supply Voltage at

Previous Fault

PowerSupply Volt

Displays the power supply voltage at the previous fault.

Displayed as in U1-54.

No signal output

available

1 V

U2-58

(0847)

Power Supply

Frequency at Previous

Fault

PowerSupply Freq

Displays the power supply frequency at the previous fault.

Displayed as in U1-58.

No signal output

available

0.1 Hz

<1> Display is in the following units based on drive model:

2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0414: 0.1 A units

<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.

u

U3: Fault History

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U3-01 to

U3-04

(0090 to

0093

(0800 to

0803))

First to 4th Most Recent

Fault

Fault Message o

Displays the first to the fourth most recent faults.

Refer to Fault Trace Contents on page 408

for details.

No signal output

available

U3-05 to

U3-10

(0804 to

0809)

5th to 10th Most Recent

Fault

Fault Message o

Displays the fifth to the tenth most recent faults.

After ten faults, data for the oldest fault is deleted. The most

recent fault appears in U3-01, with the next most recent fault

appearing in U3-02. The data is moved to the next monitor

parameter each time a fault occurs.

Refer to Fault Trace Contents on page 408

for details.

No signal output

available

U3-11 to

U3-14

(0094 to

0097

(080A to

080D))

Cumulative Operation

Time at 1st to 4th Most

Recent Fault

Elapsed Time o

Displays the cumulative operation time when the first to the

fourth most recent faults occurred.

No signal output

available

1 h

U3-15 to

U3-20

(080E to

0813)

Cumulative Operation

Time at 5th to 10th Most

Recent Fault

Elapsed Time o

Displays the cumulative operation time when the fifth to the tenth

most recent faults occurred.

No signal output

available

1 h

U3-21

(300B)

Date Year at Most

Recent Fault

Fault 1 YYYY

Displays the year when the most recent fault occurred.

No signal output

available

U3-22

(300C)

Date Month and Day at

Most Recent Fault

Fault 1 MMDD

Displays the date and day when the most recent faults occurred. No signal output

available

U3-23

(300D)

Time Hours and Minutes

at Most Recent Fault

Fault 1 HHMM

Displays the time when the most recent fault occurred.

No signal output

available

B.14 U: Monitors