Three-Phase 480 Vac Models B096 to B414

Table A.3 Power Ratings Continued (Three-Phase 480 V)

Item

Specification

Bypass Model Z1D1

B096

B124

B156

B180

B240

B302

B361

B0414

Maximum

Applicable

Motor

Capacity

<1>

HP

75

100

125

150

200

250

300

350

Input

Input Current (A)

<2>

88

114

143

165

219

276

330

378

Rated Voltage

Rated Frequency

Three-phase 480 Vac 50/60 Hz

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency Fluctuation

±5%

Output

Rated Output Current (A)

96.0

<3>

124

<3>

156

<3>

180

<3>

240

<3>

302

<3>

361

<3>

414

<3>

Overload Tolerance

120% of rated output current for 60 s

150% peak

Carrier Frequency

User adjustable between 4 and 10 kHz

(Maximum Frequency varies with Rated Output Capacity)

Maximum Output Voltage (V)

Three-phase 480 V

Maximum Output Frequency (Hz)

400 Hz

EMC

Filter (IEC/EN 61800-3 Category 2)

Built-in

<1> The motor capacity (HP) refers to an NEC Table 430.250 208 V motor. The rated output current of the drive output amps should be equal to or

greater than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance.

<3> Carrier frequency is set to 4 kHz. Current derating is required to raise the carrier frequency.

A.1 Power Ratings

302